I'm not talking about the safety of different ways of doing three phase. I'm taking it as a given that three phase is wye ground and optimal for safety. My po
by Dylan16807 7mo ago
I'm not talking about the safety of different ways of doing three phase. I'm taking it as a given that three phase is wye ground and optimal for safety.
My point is that in the context of a 230V single phase circuit, your ground is no longer in the middle. The ground is on one end of your single phase. If you want a safer single phase, you need to rebalance it to +115 and -115.
- jcalvinowens 7mo agoI thought they meant a "two phase" service where the two phases are 120 degrees out of phase instead of 180, like an apartment fed with two poles of a 208V wye with 120V to neutral/ground, which is balanced. If it's just a single phase, you're right.
- Dylan16807 7mo agoEU power is ~230V on a single phase and ~400V between phases. So a house usually gets three phases, but the only appliance where the voltage to ground is less than the total voltage is probably the oven.