Could someone explain why the frequency drops during heavy load? The voltage drop makes sense but I would think the frequency would remain fixed because the pow
by nradov 9y ago
Could someone explain why the frequency drops during heavy load? The voltage drop makes sense but I would think the frequency would remain fixed because the power plant generators still spin at the same RPM.
- pjc50 9y agoNot necessarily, no - the generator speed is a function of input shaft power versus demanded electrical power, and if the power plant can't or won't increase the feed of coal/gas and hence steam to the turbines, the generators will slow down. (In most countries you can see a little bit of a frequency dip at times of high demand. It also has the effect of reducing the power draw by synchronous AC motors.)
- Symbiote 9y agoAs an example, this site shows information about the British power grid. The frequency is currently 50.034Hz, at some point it will be below 50Hz to keep the average at 50Hz. http://gridwatch.templar.co.uk/ http://gridwatch.templar.co.uk/
- Reason077 9y agoThat's right. Grid frequency in the UK can be used as a signal indicating the real-time balance of supply and demand. When the frequency drops below 50Hz, it suggests that demand is outpacing supply, and vice-versa when the frequency is above 50Hz. Grid voltage can vary due to your location and all sorts of factors, but frequency is, of course, always synchronised wherever you are. National Grid pays a lot of money for "frequency response" to ensure the grid remains balanced. Traditionally this was provided largely by coal spinning reserve. But as most coal-fired plants have now closed, it's now provided by diesel farms (yuck!) and increasingly, battery storage. http://www2.nationalgrid.com/uk/services/balancing-services/frequency-response/ http://www2.nationalgrid.com/uk/services/balancing-services/...
- Caveman_Coder 9y ago> "When the frequency drops below 50Hz, it suggests that demand is outpacing supply, and vice-versa when the frequency is above 50Hz." As a former Transmission System Operator I can tell you the most likely scenario you see this is when generation trips offline (demand exceeds supply for a short time). I've sat in an Arizona control room, 1700MW of NW hydro would trip offline and we'd see a massive drop in interconnect frequency.
- danans 9y ago> National Grid pays a lot of money for "frequency response" to ensure the grid remains balanced In the US frequency response is mostly Nat Gas powered. There are new projects that are battery based, but another way to achieve this is on the demand side, by requesting non critical loads to turn off or throttle themselves when the frequency drops too low. I think this is being done at an industrial scale (i.e aluminium smelters) but it is possible on the domestic scale also with EVs electric tank water heaters, etc. Going forward, given the intermittency of renewable energy, these methods (primarily storage) will be more important as the energy supply becomes more variable.
- Caveman_Coder 9y ago> "...by requesting non critical loads to turn off or throttle themselves when the frequency drops too low." I'm not sure about other utility companies, but when I was a TSO we never did this. For the most part, AGC worked fine to maintain frequency. http://www.nerc.com/files/bal-005-0_2b.pdf http://www.nerc.com/files/bal-005-0_2b.pdf
- danans 9y agoAutonomous Demand Response for frequency regulation is real, and being pursued as a way to deal with the intermittency of renewables and the resulting impact on grid supply. Here are some references: General Topic: http://www.pnnl.gov/main/publications/external/technical_reports/PNNL-21152.pdf http://www.pnnl.gov/main/publications/external/technical_rep... http://www.sciencedirect.com/science/article/pii/S0196890416306276 http://www.sciencedirect.com/science/article/pii/S0196890416... HVAC Demand/Response: http://ieeexplore.ieee.org/document/7407597/?reload=true http://ieeexplore.ieee.org/document/7407597/?reload=true Aluminum Smelter Demand Response: http://repository.cmu.edu/cgi/viewcontent.cgi?article=1836&context=dissertations http://repository.cmu.edu/cgi/viewcontent.cgi?article=1836&c...