fully agreed here, especially leave yourself room for when you misjudged some resource utilization (and need more). Nothing worse than having a resource crunch
by spydum 10y ago
fully agreed here, especially leave yourself room for when you misjudged some resource utilization (and need more). Nothing worse than having a resource crunch (cpu/mem/io) and not being able to resolve it because your rack is out of power/cooling/etc - you'll come to appreciate how easy it was in cloud just clicking the button and turning out your wallet.
- sytse 10y agoGreat points. We'll make sure to wire to separate power feeds that can both handle the entire load. Suggestions in how to calculate this? Taking the maximum rated load seems over the top.
- DanielDent 10y agoYou can certainly do some math/estimates based on looking at individual component specifications, but I like using a power meter (built in to some PDUs - which is a feature worth having, or you can buy one, they are quite inexpensive). A system at idle vs full CPU vs full cpu + all disk will produce very different measurements. Also keep in mind 80% derating - many electrical codes will state that an X amp circuit should only be used at 0.8X on a continuous basis (and the circuit breakers will be sized accordingly).
- KenoFischer 10y agoI recently had to do this. The server I was putting up was rated for 3kW. To determine the expected load, I put it under a dummy load that I reasonably considered the maximum for what I would expect on the server (this was a dev machine, so I picked compiling the linux kernel as a benchmark). I ran that until the power stabilized (SuperMicro servers can measure power consumption in hardware and expose this via IPMI - very handy), because power consumption may keep creeping up for a few minutes as the fans adjust to the new operating temperature. I then repeated the same exercise with a CPU torture test (Prime95), just to see what the maximum I could possible get out of the machine was. The numbers turned out to be about 1.8kW for the linux kernel benchmark, and 2.3kW for the torture test. What I ended up doing was to provision for 2kW and use the BIOS' power limiting feature to enforce this. That would kill the machine if it exceeded its designed load, but that's usually better than tripping the breaker and killing the entire circuit. You may also want to talk to your data center provider about overrages. Some of the quotes I got wouldn't kill your circuit when you went over, but would just charge you (a crazy amount, but better than losing all your servers). Hope that helps. Your deployment is larger than ours, so there may be other techniques, but that's what we did.
- toomuchtodo 10y agoPrime95! I haven't seen that since 2000-2001! Solid tool for burning in a box and putting the CPU under maximum load.
- sytse 10y agoI love the idea of killing the server instead of the circuit, thanks!
- BuuQu9hu 10y agoMight be better to just throttle the CPU/etc when too much power is being used.
- Rapzid 10y agoAt RS we would burn the servers in measure the load with a clamp meter. For large scale build-outs(swift, cloud servers) we would burn-in entire racks and measure the load reported by the DC power equipment. I would recommend verifying everything is fault tolerant/HA as expected every step of the way. We ran into issues where the power strips on both sides were plugged into the same circuit(D'oh), wrong SST's, redundant routers getting cabled up to the same power strips, etc and you name it. After a rack is setup have people at the DC(your own employees or the DC's techs) help simulate(create) failure in power, networking, and systems to verify everything is setup correct. It sounds like you have people coming onboard with experience provisioning/delivering physical systems though, so I would expect them to be on the ball with most of this stuff.
- sytse 10y agoThanks, that is very helpful. And we haven't made these hires yet but we hope we can in the coming months.
- __d 10y agoFor HP gear, use HP Power Advisor utility. For Dell, see the Data Center Capacity Planner. Not sure what SuperMicro has -- check with your VAR.
- zonywhoop 10y agoHaving designed and run colo data centers for many years my rule of thumb for calculating this for customers was to use the vendors tools if available or take 80% of power supply rating. Keep in mind that most servers will have a peak load during initial power on as the fans and components come online and run through testing. If a rack ever comes up on a single channel and the circuits are not rated right that breaker will just pop right back offline and you'll have to bring it up by unplugging servers and bringing them up in sets. Also most breakers are only rated at 80% load so you have to de-rate them for your load. So, e.g., a 20amp x 208 3 phase circuit really only has 8KW of constant power draw available.
- late2part 10y ago+1. As tempting as it is to say "oh this server only needs full power when it boots" this may come back to bite you. As you grow usage in CPU and Disk, the power used by the server will increase substantially.
- late2part 10y agonote that you can get around the 80% breaker limit by having your DC hardwire the power, if you have enough scale to have them do this for you.
- DanielDent 10y agoCircuit breakers aren't just there for the amusement value of watching a clustered system go into split-brain mode... I.e. you would also want to be sure that your wiring was rated for 100% utilization, and that other circuit-breaker-like functions exist. Fire is an actual thing, and figuring out the best way to recharge a halon system isn't exactly what you want to be doing.
- late2part 10y agoYes. That's why they hardwire and use a breaker rated at 100%. In most jurisdiction, code requires breaker at 80% if a plug/receptacle is used. If you are hardwired you can use 100% of your capacity before tripping the breaker. You have incorrectly assumed that I suggested that you ignore breakers. When you hardwire the circuit the electrical code allows you to use a 100% breaker.
- late2part 10y agoyou want 2*N Power feeds where N = 1 or 2. I recommend ServerTech PDUs. You'll want to factor in the maximum load, but with the amount of servers and power you're doing, you should be able to negotiate metered power at under $250/kW/month. Give them a commit that's 1/3 of your TDW/reportd power load, and then pay for what you use.