Dry soil can be enough, but more likely, yes, there is probably an anti-corrosion coating. Either way, a ground clamp, a piece of #8-#4 bare copper, and an 8'
by CapitalistCartr 12y ago
Dry soil can be enough, but more likely, yes, there is probably an anti-corrosion coating. Either way, a ground clamp, a piece of #8-#4 bare copper, and an 8' ground rod, will solve the problem.
- mschuster91 12y agoCopper? In plain earth? That will only give you complete corrosion in, depending on conditions, not even a whole year. Usual standard is zinc-coated steel, 10mm (or larger, depending on stuff like attached lightning protectors, the diameter of the supply line and a number of other factors).
- CapitalistCartr 12y agoThe connector wire is copper, sized from #8 to #4. The ground rod is 5/8" galvanized steel. That's the standard ground in the USA since water pipes went to PVC. And the copper will last underground indefinitely. As mschuster91 said, there is always a risk of hitting existing lines when driving a rod in the ground.
- mschuster91 12y agoAh, the connector. Sorry, misunderstood you - I thought you meant the entire thing to be made out of copper.