3 ms·
Brian from Backblaze here. > they are using really wide raid6 stripes,... no hot swap ability. SATA drives are inherently hot-swappable, you can hot swap driv
by brianwski 12y ago
Brian from Backblaze here.
> they are using really wide raid6 stripes,... no hot swap ability.
SATA drives are inherently hot-swappable, you can hot swap drives in a Backblaze Storage Pod if you want to. In our datacenter for our particular application we just choose not to. We shut down the storage pod, calmly swap any drives that failed, then boot it back up. The pod is "offline" for about 12 minutes or there about. The RAID sync then happens as the pod is live and the pod can be actively servicing requests (like restoring customer files) while the RAID sync occurs.
- KaiserPro 12y agoInteresting, do you find that the power up causes more disks to pop? (with the change in temperature?) How often do you see multi-drive failures(in the same lun)? We've just past a peak of drive failures (had a power outage) where we've had multi-drive fails in the same lun. The awesome part about that is that each rebuild caused more drive to fail. I think one array swallowed 5 disks in two weeks. It didn't help that the array was being hammered as well as rebuilding (70 hour rebuilds at one point)
- brianwski 12y agoAnytime we reboot a pod, it runs a "significant" risk of not coming back up for a variety of reasons, and if a pod is powered off for several hours it is even worse. My completely unfounded theory is cooling off and heating back up is bad, short power downs things don't really cool off as much. > How often do you see multi-drive failures(in the same lun)? It happens - usually for a reason. Most recently a bunch of drives of one model all seemed to fail very closely together after running for 2 years, it's like some part wore out like clockwork. We are pretty relaxed about 1 drive popping, nobody gets out of bed and runs to the datacenter for that, it can wait until the next morning (the pods instantly and automatically put themselves in a state where customers can prepare restores but we stop writing NEW data to them to lighten the load on the RAID arrays). So if 2 drives fail within 24 hours on a Sunday then Monday morning we go fix it. > each rebuild caused more drives to fail. Same exact experience here, we feel your pain. We even have a procedure where we line up all brand new drives, clone each individual original drive to a new drive, then take all the new drives and insert them back into the original pod AND THEN run the RAID rebuild.
- rincebrain 12y agoYou may find "Datacenter Scale Evaluation of the Impact of Temperature on Hard Disk Drive Failures" relevant to your theory.