6 ms·
Network Instability in NYC2 on July 29, 2014
- korzun 12y agoGood post. This is essentially the risk you face when dealing with new providers. I guarantee that other providers had to go thought the same set of issues and phases prior to achieving a truly redundant infrastructure. Would love to hear a follow up on the audit. Edit: Misread a part of the post. Thought they were doing fail-over on a different network level.
- samplonius 12y agoDon't schools teach reading comprehension these days? "... the solid state disk in the active routing engine failed on one of our core switches. This triggered a failover to the backup routing engine..."
- benjamincburns 12y agoFWIW, this response might've been upvoted rather than downvoted if not for the snark.
- sard420 12y agoPretty common for router/switch manufacturers to include just 1 storage device (SSD/CF/whatever). That's one reason why you buy the second router/switch for redundancy.
- korzun 12y agoThanks. Corrected my post. For some reason I thought failure point was outside of the actual switch appliance.
- donavanm 12y agoSo an RE failed and flipped to the secondary. They run mlag from the agg layer to their tors. Said mlag had a grey failure. The time to recovery was predominantly fault detection. After detection they upgraded the os on the known good switch. Presumably this bounced, affecting remaining traffic. After upgrade they downed the failed switch, shifting traffic to the known good. Moderately interesting that they run everything off a single agg pair. Also that they use mlag instead of routing/mpls/etc for availability. Key finding is lack of visibility in to the layer 2 availability and performance. Would be interestin to see if they try to ecmp layer 3 or use existing lacp frames for fault detection in the future.
- insaneirish 12y agoThey're probably learning that MLAG should be avoided unless absolutely necessary. But providing common L2 domains across cabinets is probably something they "need." There's much less to go wrong with ECMP at L3. Stateful networking components frighten me.
- donavanm 12y agoNot knowing anything about their infrastructure Id guess that they're using vlan tags for customer isolation. They'd want customer instances spread among racks, based on instance type etc. Going to in house/vxlan/nvgre encap certainly looks better suited, but still has a high bar to entry.
- contingencies 12y agoYou guys sound like you know a lot about these types of networking protocols. Can you recommend a decent summary of currently available approaches to relatively dynamic private link layer network topology provision suitable for cross-cabinet (or even cross-site) virtualized infrastructures and their drawbacks? For instance, I've been seeing Open vSwitch gaining popularity.
- Donzo 12y agoWhile the outage was upsetting, the response from DO was reassuring. Not only did they jump right on the problem, they maintained communication during the affected period. Then, they refunded me $160 (a month of service). Every host has an occasional problem. It's how they handle the problem that is important to me. This is a night and day contrast compared to the service I received with other hosts with which I've dealt.
- pnmahoney 12y agowas this other people's experience? e.g. getting a refund?
- nieve 12y agoI only keep three machines with them, but two are in NYC2. For the July 24th outage they issued a combined 4¢ SLA credit for claimed two hours downtime. For this much worse problem? Nada. I suspect that DO is prioritizing refunds for more lucrative customers and if you're not spending enough you're not going to get anything. I may need to look into moving some stuff over to Ramnode if they've got a NYC location now (Wall Street clients).
- bogomipz 12y agoI find it alarming that they don't have a competent network engineer of their own on staff. Note the following: "We are working very closely with our networking partner to understand the nature of the failure, assess the chances of a repeat event, and to begin planning architectural changes for the future." "Our initial focus was on verifying the configuration so we initiated a line-by-line configuration review by engineers at our network partner" Yikes. You get what you pay for.
- imbriaco 12y agoWe have very competent network engineers, but it never hurts to have a second opinion. Verifying that there are no subtle interactions that we've missed is simply prudent. At our scale, partnering with our vendors is a necessity. We often operate in areas that, while they are technically within specification, are toward the higher end of the range.
- jwatte 12y agoWhich vendor? I have experience with two brands in similar condos, one good, one not so much...
- imbriaco 12y agoI prefer not to publicly name the vendor. This is about problems on our network, and it's ultimately our responsibility.
- insaneirish 12y agoI urge you to seriously reconsider your design. VPC/MLAG/etc. are attractive because of the ease of making any VLAN available anywhere without the traditional spanning tree nightmare of doing so. However, you're trading one nightmare for another. Your core or aggregation switches are now stateful, and you've just experienced the results of stateful network components not failing cleanly. I'm not saying an overlay (e.g. VMware NSX née Nicira) is the solution either. I'd suggest rethinking why you need any VLAN anywhere, which is likely the reason for VPC/MLAG. If I'm wrong and you don't put the same VLAN in multiple cabinets, then rip VPC/MLAG out immediately and switch to a pure L3 design. It is so much simpler and consistent with industry best practices.
- snewman 12y agoA good postmortem... and a clear example of a Type 1 Outage. There are pretty much only two kinds of outage in a decently-run system: 1. Two or three things go wrong at once. Some of the problems are spontaneous, and some were always broken but it took the other problem(s) to uncover it. (Here, the SSD failure was presumably spontaneous, but the "not completely successful" routing engine failover sounds like a case of rarely-used-hence-poorly-tested.) 2. A systemic failure hits all redundant components at once (DDOS, fat-fingered global configuration change, calendar bug, etc.)
- akg_67 12y agoThe network problems seem to have started earlier. I received a penny for my NYC2 droplet just before this major incident. Luckily, I decided to shutdown and move the droplet to SFO before this incident. Over the last couple of years dealing with cloud providers, I have learned to dust off the contingency plan as soon there is whiff of issues at a location. Though the recap is good, there are red flags that show gaps in DO processes and incident management. Upgrade of software before the original problem was diagnosed and resolved. This is a big no-no, never introduce a new variable in an existing problem even if the service provider or lab testing shows the chances of failure are minimal. I have worked long enough with technology infrastructure to experience situations where service provider insisted on upgrading software during unrelated incident and made situation worse. A better approach would have been to fail the network to good switch first and when the bad switch was fixed, upgrade the software on bad switch first then failover to the upgraded switch and upgrade software on good switch. This time you guys got lucky but sooner or later your luck will run out.
- imbriaco 12y agoGenerally speaking I agree with you. However, in this specific case there were a couple of reasons we chose the path we did: 1. We had experienced bugs with the currently running release which we were fairly sure would manifest when we removed the damaged core from the network. These were primarily around MAC learning. 2. We had performed testing ourselves in a non-production environment and were already planning to take a network maintenance to update these switches in the next few days. Given those factors, we judged that introducing another variable in the new version was less risky than proceeding with the defects that we knew about in the existing version.