2 ms·
You want to be able to EPO without agent (e.g. if someone's being electrocuted; especially with something like Halon 1301, you want to be able to remain in the
by rdl 14y ago
You want to be able to EPO without agent (e.g. if someone's being electrocuted; especially with something like Halon 1301, you want to be able to remain in the room to give medical aid), but I've never heard of room-scale agent dump without EPO (either interlocked or as a checklist procedure).
The problem with that is that you only get one shot with the agent (although everywhere I've seen has a gas/clean agent with dry-pipe water as the true final protective measure). If there's electricity still going in, and you use your one shot with the facility clean agent, you might not actually put out the fire, or it could re-ignite, and then you either have no fire protection or only water. The cost of filling a datacenter with water, especially one important to have gas and water backup in the first place, is huge, even relative to an EPO pull.