Not a data centre expert, but don't they quite famously pump CO2 into the server rooms automatically if the fire alarms go off, even if there are people in the
by AussieWog93 2mo ago
Not a data centre expert, but don't they quite famously pump CO2 into the server rooms automatically if the fire alarms go off, even if there are people in the room?
- dividedbyzero 2mo agoThat's not always a thing and doesn't help with fires in the rest of the complex. Backup generators, fuel depots, power distribution, large-scale cooling infrastructure all pose fire hazards even when facilities are built with actual regulation. The current AI buildout in the US happens pretty much without any meaningful regulation and gives the impression they'd build unshielded nuclear reactors serviced by children while running if they felt they could get it running cheaper and faster.
- trollbridge 2mo agoYes, that’s exactly my impression. When regulations do exist they use political means to try to evade them for a 1% cost savings.
- officeplant 2mo agoC02 fire suppression is rare in datacenters. That's more of an offshore thing in my experience (I design fire suppression systems for a living, and do life safety systems). Typically server rooms are currently Fluoro-K / Novec123 if they have space constraints on the suppression systems. Those cylinders take up the least space per cubic foot of protected environments. These are less harmful than previous gasses like Halon, but still not good for the environment. If you're lucky we get given ample room for cylinders and can go with Argon suppression systems, but that can take up more than 4 or 5 times the space alone and adds a lot of cost in engineering manifolds, etc. CO2 takes up as much space as Argon systems and will kill someone who doesn't leave the hazard area before release so its generally not used in any datacenter project I've done. Powerplant's at datacenters often use drychem systems instead or foam releasing systems.