The "standard" wiring is 1.5mm² on 16A MCBs which are rated to trip at 1.13-1.45x nominal current (so 18-23 A). So this is already mildly improper because you c
by formerly_proven 7mo ago
The "standard" wiring is 1.5mm² on 16A MCBs which are rated to trip at 1.13-1.45x nominal current (so 18-23 A). So this is already mildly improper because you can pull elevated currents continuously and dramatically shorten the life of the insulation.
- kevin_thibedeau 7mo agoThe rated ampacity of wire for electrical distribution has a significant margin on it.