I guess it's possible to have a condensing station, but generally speaking you'd need to supply input energy to allow it to cool down and condense somehow. The
by sidewndr46 9mo ago
I guess it's possible to have a condensing station, but generally speaking you'd need to supply input energy to allow it to cool down and condense somehow. The bigger question here is if a datacenter using evaporative cooling where does the moisture go? If it just feeds a cloud system that rains on nearby fields, it's not much different than irrigating crops. If it feeds clouds that go offshore and rain into the ocean, it's similar to just diverting drinking water into the ocean
- 306bobby 9mo agoI must be missing something, why can't it be entirely closed loop like a water radiator in an old car? A simple fan running through large radiator cores would certainly condense within the system, keeping the water in the system
- quickthrowman 9mo agoA closed loop system has a COP of 4, adding in cooling towers almost doubles that to 7. You can reject 1.75x more heat for the same amount of electricity by adding evaporative cooling towers. COP is coefficient of performance.
- pfdietz 9mo agoOne thing to remember is that much of the waste heat from your car's engine goes out the exhaust, not out the radiator. I think the two are often about equal.