Baseboard heaters are often sized such that very high temps are needed (because that's what cheapest/lowest labor/least space used), but they don't have to be s
by sokoloff 2y ago
Baseboard heaters are often sized such that very high temps are needed (because that's what cheapest/lowest labor/least space used), but they don't have to be sized that way. In the attic bedroom, we have baseboards around the entire perimeter on two walls and same in the bath. I run the attic zone on the same water temp (outdoor reset controlled to be quite low) as the rest of the house (mostly large cast iron rads, one cast iron convector). Good insulation and air sealing in the attic means that the attic zone calls way less than the downstairs.
- looofooo0 2y agoWhich is not exactly efficient. 40C or less is desirable.
- sokoloff 2y agoMy return water temps are 115F (46C) on a P98 design heating day, and obviously cooler on warmer than design days. Cooler is always better, but "baseboards require 180F [82C] water because that's what's on the spec sheet" is a commonly-held but mistaken belief.
- looofooo0 2y agoThis is bad. Return water should be less 35 degree max. Actually 30 degree after the heat pump would be ideal: https://www.flow30.de/ https://www.flow30.de/
- jillyboel 2y ago[citation needed]
- looofooo0 2y agoAh this is school knowledge of thermodynamics: the smaller the delta the more efficient the heat pump. For human comfort look at the iso7730. Also the system is self regulatory with such low temps.
- Retric 2y agoHeat pumps and furnaces behave very differently here. For a furnace you’re talking fractions of a percent difference in efficiency across a wide temperature range so by far the most critical issue is total heat losses to the outside. A heat pump’s efficiency is far more variable making total losses to the outside less important.
- looofooo0 2y agoFirst, sooner or later you have to replace your furnace with a heat pump. Second, modern furnaceses are condensing. Return temp should be as low as possible maximise condensing.
- Retric 2y agoWe agree return temps should be lower, but to determine how critical this is you need to out numbers on that. In steady state operation at maximum load a difference in return temperatures of 15f is ~1% efficiency. But steady state at maximum load is an extreme situation the average return temperature is well below that theoretical maximum thus an even wider difference is needed for a seasonal difference of 1%. Redundancy is critical in areas that get really cold. That may eventually mean turning to hydrogen, but a backup gas furnace for a well insulated home really isn’t a major CO2 contributor. More relevant to the discussion it further reduces the impact of minor changes in efficiency or comfort.
- looofooo0 2y agoAs said, at some point you will likely replace your furnace by a heat pump. Then all investment to low temperatures will pay off. A modern gas furnace is no backup for a heat pump, as it also needs electricity. I would recommend a low tech solution like a wood stove for backup. I have one in my cellar. In case of a long power outage I would likely just install this through some open window and do some redneck stuff to make it airtight.