While technically true, the NEMA 5-15R receptacles are rated for use on 20A circuits, and circuits for receptacles are almost always 20A circuits, in modern con
by theturtle32 2y ago
While technically true, the NEMA 5-15R receptacles are rated for use on 20A circuits, and circuits for receptacles are almost always 20A circuits, in modern construction at least. Older builds may not be, of course.
That said, if your load is going to be a continuous load drawing 80% of the rated amperage, it really should be a NEMA 5-20 plug and receptacle, the one where one of the prongs is horizontal instead of vertical. Swapping out the receptacle for one that accepts a NEMA 5-20P plug is like $5.
If you are going to actually run such a load on a 20A circuit with multiple receptacles, you will want to make sure you're not plugging anything substantial into any of the other receptacles on that circuit. A couple LED lights are fine. A microwave or kettle, not so much.
- andrewmcwatters 2y ago> and circuits for receptacles are almost always 20A circuits, in modern construction at least. This is not true. Standard builds (a majority) still use 15-amp circuits where 20-amp is not required by NEC.
- bliteben 2y agoYes, almost all post 2000 houses will have 20 amps in kitchen but in many areas the other circuits will be 15 amp.