Generators must synchronize with the grid. Huge spinning rotor masses that will experience tremendous forces to coerce them into matching an RPM that correspond
by xenadu02 2y ago
Generators must synchronize with the grid. Huge spinning rotor masses that will experience tremendous forces to coerce them into matching an RPM that corresponds to the grid's frequency.
Frequency is also impacted by load: the greater the load on the generator the more torque required at its input shaft to maintain the same RPM. If the generator's input engine is already at max torque then RPM must decrease all else equal. That in turn requires that every other generator on the grid also slow down to match.
When a huge chunk of generating capacity disappears there isn't enough power feeding the remaining generator input shafts (all else equal) to maintain RPM so the grid frequency must drop. That tends to destroy customer equipment among other problems.
Generators are motors and motors are generators. If the capacity disappears too quickly the grid _drives the generator as a motor_ potentially with megawatts of capacity all trying to instantly make that 100 ton rotor change from 3600 RPM to 2800 RPM or whatever. Inertia puts its $0.02 and the net result is a disintegrating rotor slinging molten metal and chunks of itself out while the bearings turn into dust.
Protective equipment sees this happening and trips the generator offline to protect it. Usually the coordinating grid entity keeps spare capacity available at all times to respond to loss of other capacity or demand changes. This is also the point of "load shedding": if spare capacity drops below a set level loads are turned off.
If spare capacity is not maintained or transmission line choke points present problems then capacity trip outs can cause progressive collapse as each generator sees excessive load, trips, and in turn pushes excess load to the next generator. If your grid control systems are well designed they can detect this from a central location and command parts of the grid to "island" into balanced chunks of load/capacity so the entire grid does not fully collapse.
Of course when you want to reconnect the islands it takes careful shifting of frequency to get them aligned before you can do that.
If all generators collapse you end up in a black start situation that requires careful staging lest more load than you expected jumps on the grid (maybe due to control devices being unpowered or stuck somewhere), triggering a secondary collapse.
Caveat: not a grid engineer so I may have gotten some of this wrong but hopefully it helps anyone who wonders why load shedding exists or how a grid can "collapse" and what the consequences are if you don't do those things and just let it ride.
- raggles 2y agoAm grid engineer. You nailed it. It can get incredibly complex modelling this stuff, and reading all the armchair observers banging on about 'single points of failure' is amusing.
- xenadu02 2y agoOh yeah. These posts are the limit of my knowledge. Real-world power plants, switchgear, and grid management is way way more complex! And if you want to talk about "hard real time requirements".... it doesn't get much harder or real time than keeping the grid going :) Thanks to you, the operators, and the linemen out there keeping it all going. When it works correctly no one notices.
- wglb 2y agoMy professor did that for Bonneville Power Administration. I worked on a tiny piece of his modelling software. A short writeup of it https://ciex-software.com/fmcmx.html https://ciex-software.com/fmcmx.html
- shepherdjerred 2y ago> the grid _drives the generator as a motor_ Can you expand on this/link a relevant article? I'm a layman and this sounds really interesting!
- xenadu02 2y agoTake a little hobby DC motor and hook it to a battery. It will spin. Now hook it to a small LED and turn the shaft. The LED will light up. In fact hook both up. The battery will spin the motor and light the LED based on its voltage/charge state. But if you start spinning the shaft you will begin taking over from the battery. Spin even faster and the battery will start charging. Stop trying to spin the shaft and watch the LED dim and the motor slow down as the battery takes over again. Fundamentally electromagnetism is a unified force. A changing electric field induces a magnetic field: the electricity creates a magnetic field inside the motor-generator causing the rotor's electromagnet or permanent magnet to spin to align with that field. For a DC motor halfway through the rotation the polarity switches causing the rotor to keep spinning to align with the new magnetic field (AC doesn't need this because it is varying on its own). The motor-generator is operating in "motor" mode here because the magnetic field changes first and the rotor is trying to catch up to it ultimately consuming energy. Now spin a motor's shaft putting energy into the system. The rotor has a magnetic field either because its an electromagnet or a permanent magnet. You are spinning the rotor shaft so by definition the magnetic field coming off the rotor also spins. Thus the stator sees a continuously varying magnetic field which - you guessed it - induces an electric field in the stator windings. In reality this is a continuously varying effect based on whether the rotor's motion is leading or lagging the magnetic field (really it is trying to lead or lag but never gets far otherwise it would burn up). The short version is a generator at "idle" but synchronized is a motor. The grid is providing the power to spin that motor (or the attached engine/steam turbine is providing just enough rotation of the shaft to keep the generator synchronized but no more). As the generator begins to "provide" power more torque is put into the shaft's rotation. This causes the magnetic field to want to lead the electric field, transferring energy into the electric field. The entire grid strongly resists the shaft actually spinning faster though. The mechanical energy that wants to make the rotor go faster is siphoned off by the magnetic flux and electric fields. Electric field steals energy from the magnetic flux. Reduced magnetic flux steals energy from the rotor's angular momentum to replenish itself (if it couldn't the rotor would slow down). The rotor gets angular momentum from the connected source of torque like a steam turbine. The Cycle of Life ... or something. If you suddenly cut the transmission lines and took no action all that torque would overspeed the generator very quickly though because no electric current could flow so the electric field just builds up (stealing energy from the rotor) then gives the energy right back as more magnetic flux (speeding up the rotor). This would let the rotor just go faster and faster while also heating everything up.