> When you work with normal AC power, it is considered unsafe practice to use parallel wires to share load in a circuit. The NEC permits using conductors #1/0A
by quickthrowman 2y ago
> When you work with normal AC power, it is considered unsafe practice to use parallel wires to share load in a circuit.
The NEC permits using conductors #1/0AWG or larger for parallel runs, it doesn’t forbid it entirely.
- DannyBee 2y agoYeah. I have 800 amp service which is basically always done with parallel 400 mcm or 500 mcm (depending on where it is coming from, since POCO doesn't have to follow NEC) Within conduit, there is basically no other option. In free air there are options (750 mcm, etc). Even if there were, you could not pay me to try to fish 750 mcm through conduit or bend it
- quickthrowman 2y agoYeah, (2) sets of 4”C 4#500MCM #1/0G (copper) is typical for an 800A service. My electricians feel the same way as you do about anything over #500, usually for 400A we parallel #4/0 instead of one set of #500.