This quote from the article annoys me… > … it proposes to require the same exact ground-fault circuit-interrupter protection that makes you push that little bu
by pugworthy 2y ago
This quote from the article annoys me…
> … it proposes to require the same exact ground-fault circuit-interrupter protection that makes you push that little button on your bathroom outlet every time the curling iron won’t heat up.
Specifically if your GFCI in the bathroom (or anywhere) keeps tripping it’s because something is wrong with your wiring or something plugged into the outlet.
It took some restraint to not use all caps in part of that sentence.
- jaggederest 2y agoAnd that GFCI might be the only thing keeping you from being electrocuted every time the curling iron won't heat up. Standing in a puddle touching a metal pipe casually confused by why it sometimes tingles.
- exmadscientist 2y ago> Specifically if your GFCI in the bathroom (or anywhere) keeps tripping it’s because something is wrong with your wiring or something plugged into the outlet. Unfortunately this is not quite true. For two-prong plugs, yes, it is 100% accurate. However larger devices with grounded plugs, especially heavier machinery, will typically contain a line filter with Y capacitors running line to ground. This shows up as a tiny leakage current, which some GFCIs will detect (because it really is leaking) even though this is a nuisance trip (because it is completely safe and normal operation). That's part of where the 30mA trip specification for certain types of non-normal-residential-circuit comes from.
- pugworthy 2y agoFair enough but it’s not the best example to use to introduce GFCI. Something like this? “Though you rarely will see your bathroom GFCI trip (unless you’re dropping the hair dryer into the bath water), some kinds of larger, more complicated machinery can cause nuisance trips.”
- exmadscientist 2y agoSure, I wouldn't normally go there, but the subject of this discussion is exactly the "larger, more complicated machinery"!
- mike_d 2y agoYou are talking about industrial applications. Devices running in residential or commercial environments should be better designed. Proper shielding and grounding is a much better solution than a Y capacitor.
- exmadscientist 2y agoWell, they aren't. Line filters are everywhere. They're generally required to pass conducted emissions requirements. They aren't going away soon, and our fault protection devices need to work with them, not blindly ignore how we've been meeting EMC requirements for decades.
- timewizard 2y agoI thought it's the other way around. There are standards for line filters for precisely this case. The device is either non conforming or damaged or the power in this home is out of tolerance in one way or another.
- ethbr1 2y agoThe standard is the actual deployed base, not the book it's written in.
- amluto 2y agoA pair of matched Y capacitors on a 240V appliance from a single phase supply will cancel each other out. This doesn’t help people with 208V who are using two out of three phases, though. edit: 120V is not immune. I once worked on a project involving powering equipment in a Faraday case at 120V. The mandatory filter (to prevent the wire from conducting emissions out of the cage) instantly tripped GFCI. The right solution IMO would have been one of: a) A better filter that doesn’t pass 50-60Hz. This is doable in theory, but I’ve never seen one. b) A transformer or other isolated supply outside the cage, with a GFCI inside the cage (to protect the people who may enter to touch the equipment). c) A transformer outside, not necessarily right next to the cage, supplying the inside with two opposite-phase lines at 60Vrms each. No net leakage! This would require that everything inside accept such a supply, which rules out anything that wants a real neutral. d) I bet someone could design a transformer with a shield between the windings that would integrate with the Faraday cage. Power would couple in inductively through the shield. Common-mode RFI would have a very hard time escaping, and different mode RFI could be filtered and probably matters quite a bit less anyway. Of course, the actual solution chosen by the site’s electrical people was rather less classy.
- exmadscientist 2y agoAn ideal transformer will give you perfect galvanic isolation. A GFI therefore becomes useless on transformer secondaries, because there is no way to complete a circuit through earth back to the transformer. If you have earth grounding of stuff inside the cage (not just the cage itself)... then you have a very strange test going on. Of course, real transformers are not ideal. This: > I bet someone could design a transformer with a shield between the windings that would integrate with the Faraday cage. Power would couple in inductively through the shield. Common-mode RFI would have a very hard time escaping, and different mode RFI could be filtered and probably matters quite a bit less anyway. exists and it is called an "electrostatic shield" inside a transformer. Magnetics people do not like to make these, but they are a standard enough request that they'll do it for you and the only complaints you'll get will be from the people on your side who see the invoice. Electrostatic shields are also not perfect but they help tremendously. The shield connection usually comes out of the potted assembly on another wire so you can hook it up as required. Protip: if you are ever trying to replace or redesign equipment that uses an electrostatically shielded transformer, do ask why they went to that effort. Don't just try to use a normal transformer and then wonder why you can't get it working right... despite man-months of effort....
- pkulak 2y agoTFA explains that it’s all relative. Trying to detect 5ma of current going to the wrong place under a 48-amp load may be impossible and will probably result in constant false trips. Probably also in the middle of the night, leaving your car not charged in the morning.
- michaelt 2y ago> Trying to detect 5ma of current going to the wrong place under a 48-amp load may be impossible It's actually kinda easy - the way GFCIs work is pretty neat. You pass the live and neutral through the same magnetic field sensor. So long as none of the current is escaping to earth, you get an equal current in each direction and the total magnetic field is zero. The problem is you can get a 5mA leak to ground because of, say, condensation inside a socket. And ripping out your house's wiring in search of that is a lot of expense to deal with a relatively minor danger.
- mcoliver 2y agoOr your child loves pushing the test button
- gorlilla 2y agoIt'd be the test button. Reset puts it back into normal operation. ;)
- phire 2y agoYeah. Sounds like there something wrong with the authors wiring or curling iron. We have had whole-house GFCIs (or RDCs as we call them here) in the NZ electrical standards for 20 years, they seem to be pretty reliable, I've never seen them trip for without a reason. I have seen them trip on devices that were barely faulty. Devices which worked fine on a regular outlet, but would trip a RCD.
- russdill 2y agoThe residual current rating in NZ is 30mA. The proposed standard here would be 5mA. This seems to be one of the primary things the author in the article is calling out, that for especially heavy draws, 5mA is too low a trip point.
- Reason077 2y agoCertain devices will trip GFCIs/RCDs somewhat frequently. Toasters, for example: if a the bread touches against the live heating wires it will trip. Cordless kettles will do it if the contacts on the base gets wet or gunked up. The motor in our swimming pool cover sometimes trips after heavy rain (or excessive splashing) if it gets flooded. But I've never seen an EV charger trip an RCD!
- toast0 2y ago> Specifically if your GFCI in the bathroom (or anywhere) keeps tripping it’s because something is wrong with your wiring or something plugged into the outlet. Or the outlet itself. Some outlets end up false tripping, and need to be replaced. Probably happens with GFCI breakers, if that's where the GFCI is. Of course, normal breakers sometimes false trip and need replacement, too.
- m463 2y agoTalking to electricians, they gave me the impression that GFCI/AFCI had side-effects that were not related to an unsafe condition. Personally I've noticed buzzing or interference with some lighting on gfci circuits.
- abakker 2y agodefinitely true with dimmable LEDs. I have noticed that dimmable LEDs die in a year when running on a GFCI circuit. Solution is to find the junction and branch the switch/dimmer before the GFCI.