FM200 is not the only system available - Inergen, Novec 1230, CO2, etc (nobody has used Halon in ages if they can avoid it, as it's toxic.) Gaseous fire suppre
by KennyBlanken 2y ago
FM200 is not the only system available - Inergen, Novec 1230, CO2, etc (nobody has used Halon in ages if they can avoid it, as it's toxic.)
Gaseous fire suppression systems have numerous requirements that make them unsuited for a large publicly accessible space. There's oxygen displacement; most of them are "nontoxic" to breathe but still displace oxygen, so you have to have various measures to keep from killing people - that could range from delayed discharge up to SCBA stations (and staff training, maintenance, etc.)
The other problem is that you need sufficient concentration of the agent; the concentration varies, and some need higher concentrations (and better sealing) than others. That means quite a lot of work if the space/building wasn't built with it in mind. Even for a relatively small and simple server room, gaseous fire suppression installation is expensive and a general pain in the ass.
The systems are intended for spaces that aren't normally occupied. Vaults/storage for example, and industrial spaces (electrical substations, for example.)
- cduzz 2y agoI thought halon was "harmless" to people, but mixing halon with fire produces nasty poisons. The vast majority of fire suppression events I've heard of (in a DC or similar environment) are unintentional, meaning the halon wouldn't be toxic (according to my potentially flawed memory). Certainly, if there's been a legit fire suppression event, you wait for people with the hard-hats to clear the facility. Of course, you should do the same if there's been a no-fire suppression event, but ideally your fire suppression mechanism doesn't kill the people in the room needlessly...