Impressive that the failure of grid power (frequent) and a SINGLE GENERATOR BANK causes this much chaos on the Internet.
by rdl 14y ago
Impressive that the failure of grid power (frequent) and a SINGLE GENERATOR BANK causes this much chaos on the Internet.
- cperciva 14y agoIf I"m reading it right, it's a failure of grid power and two or more generator banks: "each generator independently failed to provide stable voltage".
- deleted 14y ago[deleted]
- rdl 14y agoAh, yeah, you're right (I was assuming they had 2 generators and needed both for the load, but it looks like they have 1+1 or N+1, probably split by room, like a real colo facility usually does).
- kalleboo 14y agoThe generator thing confused me a bit. It seems like the main issue wasn't that the generators failed, but that they took far longer to spin up than expected, so the automatic switchover failed to take, and they had to do a manual switchover at a later point (at which point the UPSes had already started failing). Or am I reading it wrong? I wonder what the additional cost would be to leave a generator running 24/7 (at minimal load), so you never have an issue with spinning them up. Are they designed to run 24/7/365, or will they wear out too quickly?
- rdl 14y agoVery high cost in both fuel (a big diesel probably uses 25% of peak fuel at idle) and maintenance (idling a lot destroys the engine), and pissing off the neighbors. You're generally not allowed to run backup generators 24x7 in most areas. It's different if you're in the middle of nowhere, but even then, maintenance issues would be prohibitive. (It would be so much fun to build a big datacenter next to a hydro dam; you'd get both pretty high availability hydro power and the HV feed going to civilization could be used in reverse to bring power if the dam goes down; pick a site where the power goes off in two directions to two grids and you've got 2 grid feeds plus local hydro plus anything like diesel onsite backup. Then you just have issues with getting diverse fiber in, but maybe along the HV routes. Northern Oregon/Southern WA is essentially this -- which is why Amazon, Google, Facebook, Microsoft, and more are putting huge facilities there.) As an aside, you need to test your generators with actual load. AC is a little more complex than just "on or off", too. The "real" way to do this is to do periodic tests with a load bank (basically a huge resistive load which converts the electricity from the generators into heat, although if you were smart, you could get big pumps and pump a pond instead, which could be used for something useful later). Most people don't, they just spin it up, or sometimes they use facility loads for test, which is good in some ways, but if the test fails, the facility load drops, which makes people sad. Backup power can fail in all kinds of exciting ways other than just not delivering power, so it's possible you'll switch to generator, generator will fail, and you won't be able to switch back, or in some cases, generator will kill your UPS and drop your load. The bigger the system the easier it seems to be for really weird things to happen, but the more individual sets of equipment you have, the higher the chances that at least one will fail in some crazy way. Which is one of the reasons the Google UPS-in-Server thing is so exciting.
- cellularmitosis 14y ago"a big diesel probably uses 25% of peak fuel at idle" I have a very hard time believing this, especially for diesels, which idle much more efficiently than spark-ignition engines. Where did you get this figure? What I'm also surprised by was the fact that they hadn't already allowed unstable voltages from the generators to be used. A modern switching powersupply can operate down to, what, 80 volts? EDIT: rdl, for some reason I can't reply to your reply. Replying here. Thanks for the info. Now that I think back, I recall reading that diesels operate with an air/fuel ratio as high as 80:1 at idle. 1/4 would put them at 20:1 at full load, which I can beleive, because diesels don't typically operate at stoichiometric even under full load, which would be ~15:1.
- rdl 14y ago2MW Cummins use about 130 gallons/hour at max load. At 1/4, about 34 gallons/hour. You can't idle them at low loads for long periods without damaging them. That's basically 1/4. You usually want it to be more like 50-75%. So "no real load" is artificially set higher than engine idle to keep the system functional, using a load bank. (what you actually do is have N generators and just use some of them, or have different sizes and use the right ones to sort of match the load) The output from the generators is going into the UPS. The UPS input is probably pickier than any switchmode power supply. Especially because most big UPSes let you set in software how picky they are about input power before they switch to battery, and they apparently had it set to conservative mode.
- mikeash 14y agoHere's something I haven't seen mentioned in the discussion yet: while it's impractical to idle the generators constantly, why not turn them on ahead of time when it appears there's a good chance of troubles with the electrical supply? The Friday storm had at least a decent hour of warning. I got an alert on my phone from the Weather Underground app, and the radar made it apparent that this was going to be a monster well before it actually hit. Their summary of the events shows that Amazon had decent warning and called in extra staff and took other precautions. So, given that they had advance warning of a potentially serious storm, why not start up the generators and have them idling beforehand? Is the cost of that still prohibitive even when it looks like there's a good chance they'll be needed?