> assuming the safety interlock is done in software It's not. There's a conflict monitor unit that is completely separate from the signal controller. It has di
by Animats 2y ago
> assuming the safety interlock is done in software
It's not. There's a conflict monitor unit that is completely separate from the signal controller.
It has direct inputs from all green or other permissive lights, and a diode matrix that determines which combinations are allowed.[1] If it detects a conflict, all signals go to flashing yellow.
"This monitor uses a standardized programming card for channel compatibility (permissives), minimum flash time, per channel Minimum Yellow Change Disable, CVM latch, and 24 volt monitor latch. Programming of this card is accomplished through the use of soldered wire jumpers. The programming card plugs into the monitor through a slot in the front panel."
All 4-way intersections use the same interlocking pattern, so there's a standard card that covers most cases. Only unusual intersections need a custom programming card soldered up.