> relied partly on the solder to hold it together You are not ever supposed to do that. I was assuming he wrapped the wires together securely first. http://en.
by ars 14y ago
> relied partly on the solder to hold it together
You are not ever supposed to do that. I was assuming he wrapped the wires together securely first. http://en.wikipedia.org/wiki/Western_Union_splice http://en.wikipedia.org/wiki/Western_Union_splice or even http://en.wikipedia.org/wiki/Rat-tail_splice http://en.wikipedia.org/wiki/Rat-tail_splice
I was just saying you don't have to use a pressure type connector - you can use a wrap splice, then solder it. (Electrical tape is not sufficient insulation, but you said this was a ground.)
- mturmon 14y agoThe NEC is even more restrictive with equipment grounding conductors, actually. You are not allowed to use solder-only connections on grounds. I don't want to go farther down the road, since we're only talking to each other, but here is a link FYI: http://www.ecmag.com/?articleID=8721&fa=article http://www.ecmag.com/?articleID=8721&fa=article The relevant part is: "Connection of Grounding and Bonding Equipment. Grounding conductors and bonding jumpers shall be connected by exothermic welding, listed pressure connectors, listed clamps, or other listed means. Connection devices or fittings that depend solely on solder shall not be used." You really cannot just twist-and-solder for a ground. It is specifically forbidden by the NEC.