This is close, and I'd grant that limit trips are associated with longer run times. But in principle continuous furnace run time shouldn't cause a high limit tr
by JesseHVAC 3y ago
This is close, and I'd grant that limit trips are associated with longer run times. But in principle continuous furnace run time shouldn't cause a high limit trip. The limit is mainly to protect the heat exchanger from damage. The primary cause is usually low/reduced airflow, although bad sensors are also common.
A high limit trip will generally cycle the furnace off for a time period. Somewhere between 3-5 off cycles will result in lockout and the furnace will stay off. The control for this is more likely to reside in the furnace board vs an aftermarket ui.