This will mean just about 4 times the number of failures, too. And can 75% cooling still cool the server room anyway?
by dotancohen 3y ago
This will mean just about 4 times the number of failures, too. And can 75% cooling still cool the server room anyway?
- donkeyd 3y agoMaybe not, but some cooling means less servers to shut down.
- bluGill 3y agoIt means 5 times the number of failures as you intentionally put in an extra unit so that one can be taken offline at any time for maintenance (which itself will keep the whole system more reliable), and if one fails the whole keeps up. The cost is only slightly more to do this when there are 5 smaller units. Those smaller units could be standard off the shelf units as well, so it could be cheaper than a large unit that isn't mad in as large a quantity - this is a consideration that needs to be made case by case) Even if you cheap out and only install 4 units, odds are your failure doesn't happen on the hottest day of the year and so 3 can keep up just fine. It is only when you are unlikely that you need to shut anything down.
- dotancohen 3y ago> Even if you cheap out and only install 4 units, odds are your failure doesn't happen on the hottest day of the year Actually, historically many HVAC failures happen when the system is running at max capacity.
- evilduck 3y agoFour service degradations vs. one huge outage event. Pick your poison.