I'm in Canada and have a 30A 240V breaker for the Debian ROCm Team's CI [1]. It's only rated for 80% continuously, so that's roughly 5.7 kW. In theory, the four
by slavik81 3y ago
I'm in Canada and have a 30A 240V breaker for the Debian ROCm Team's CI [1]. It's only rated for 80% continuously, so that's roughly 5.7 kW. In theory, the four systems currently hooked up to it could draw almost that much, but their workload only uses ~1 kW in practice.
[1]: https://lists.debian.org/debian-ai/2023/12/msg00031.html https://lists.debian.org/debian-ai/2023/12/msg00031.html