Theoretically perhaps, but practically, most single phase AC EV chargers on Europe/Australia etc. are only 7 kW but 3-phase are 11 or 22 kW (both 7 kW and 22 kW
by stephen_g 3y ago
Theoretically perhaps, but practically, most single phase AC EV chargers on Europe/Australia etc. are only 7 kW but 3-phase are 11 or 22 kW (both 7 kW and 22 kW are about 30 A per phase, but three phase you obviously have three of them, so three times the power!). That’s not “gaining nothing”!
- bluGill 3y agoWhile sometimes you get more power on 3 phase, that is only about the size of the feed and nothing to do with 3 phase.
- ajsnigrutin 3y agoBut you have three feeds giving you three phases to use, so 3x the power available to you. Out here, even electric stoves (with ovens) have 3 phase connection options and tankless water heaters almost exclusively come as 3 phase models.
- bluGill 3y agoPower is volts times amps. 3 phase just means you add the power of all three phases, but you can get the same power from one phase with a little algebra. You need different size wires and breakers, but there is nothing there that 3 phases gives you.
- ajsnigrutin 3y agoLet's say you have a cable with 2.5mm^2 wires, each of which can carry 20A of current to stay within code. At 230V that's 4600W. Now you want more power, to keep the math simple, let's say 13800W (3x the power above). With a one phase system, for 3x the power, you need 3x the size of wire, so 7.5mm^2, ie. 3x the amount of copper (since all wires, neutral and PE have to be that size too). With a three phase system, you can get the same power with 3x2.5mm^2 live wires (+1 neutral + 1 PE), so instead of 3x the amount of copper, you only need 5/3's of copper to get 3x the power.
- BenjiWiebe 3y agoNot sure what PE is in this example, but you don't need a neutral in 3 phase.
- ajsnigrutin 3y agoYou don't need it in a "triangle"/"delta" wiring, but you need it in a "star"/"Y" - https://www.electronicshub.org/comparison-star-delta-connections/ https://www.electronicshub.org/comparison-star-delta-connect... PE is protective earth, grounding wire. Usually you need PE and neutral lines separate for FID (GFCI) protection.
- stephen_g 3y agoYou’re again talking in hypotheticals and ignoring the practical factors. Around here, it’s usual for the utilities to limit residential services to 80A per phase (commercial properties can get a lot more). So for a residential property you can literally get three times as much power by upgrading from single phase (which is common for small houses) to three phase (less common around here but available) due to this limit. In theory I could just get a single phase service of three times the current, but in the real world the utility won’t give me that and makes me upgrade to three-phase. This is by policy, since it helps balance the phases in the grid back to the local transformer, which the utility wants, so they also limit, for example, how much solar export you can do per phase for residential property - theoretically I should be able to export 15 kW on a single phase, but they don’t let me, so in the real world I am limited to 5 kW per phase, meaning I can only export 5 kW on single phase or 15 kW on three phase. So in terms of pure electrical theory you are correct, but when thinking about real world policies of electrical utilities due to how power grids are designed, you do get a lot of benefit from three-phase.
- applied_heat 3y agoP=sqrt(3) IV cos Theta not just three times IV
- Gasp0de 3y agoWith three phases in Europe you get 400v, which means less amps for the same power, which means lower losses or thinner cables?
- bluGill 3y agoYou can get 400V 3 phase in the US. While houses don't, almost all commercial locations have it already. So most public chargers in the US have 3 phase available. charge at home doesn't, but those tend to be lower power charge all night vs the charge in half and hour commercial chargers.