2 ms·
> Solar inverters can produce/absorb reactive power easily > Solar and wind systems today typically do not have a voltage setpoint or control loop. That's beca
by applied_heat 3y ago
> Solar inverters can produce/absorb reactive power easily
> Solar and wind systems today typically do not have a voltage setpoint or control loop. That's because there is no big gas/steam valve to adjust the amount of power generated. The operator wants to inject all the power from the sun/wind into the grid, whatever the voltage.
reactive power being easily controlled is the same as a voltage control loop with droop when connected to a larger system.
Control of the traditional prime mover by way of devices like steam throttle valve controls real power (MW) and not voltage or reactive power (MVAR).
I am curious how an inverter operating away from unity power factor fails to deliver roughly the identical amount of energy as at unity. Can you provide a link that explains it? Traditional generators pump out the same MW barring losses due to increased current no matter the power factor. MW in mechanical * efficiency = MW out electrical. And of course there is a limit to how out of phase the voltage and current waveforms can be, usually +/- 0.9 pf.
A 60Hz cycle is 16.7 ms, A 13 kV breaker takes 80ms to open, to detect a fault (except for differential element) let alone clear it takes a lot longer than 20ms.