I think every datacenter I've ever worked with, across ~4 jobs, has had an incident report like "generator failed right as we had an outage." Am I unlucky, or
by gemstones 3y ago
I think every datacenter I've ever worked with, across ~4 jobs, has had an incident report like "generator failed right as we had an outage."
Am I unlucky, or is there something I miss about datacenter administration that makes it really hard to maintain a generator? I guess you don't hear about times the generator worked, but it feels like a high rate of failure to me.
- nik736 3y agoEven the high profile datacenters I had to deal with in Frankfurt had the same issues. There were regular maintenance tests where they made sure the generators were working properly... I can imagine this is more of a pray and sweat task than anything that's in your hands. I have no clue why this is the status quo though.
- milkglass 3y agoCost of that likely is ginormous compared to their SLA obligations.
- thedaly 3y agoThe phone utility were I live has deisel generators that kick on whenever the power goes out in order to keep the copper phone lines operational. These generators always work, or at least one of the four they have in each office does.
- bombcar 3y agoThe datacenter I was in for awhile had the big gens, and with similar "phone utility" setups - they would cut to the backup gens once a month and run for longer than the UPS could hold the facility (if they detected an issue, they'd switch back to utility power). They also had redundant gensets (2x the whole facility, 4x 'important stuff' - you could get a bit of a discount by being willing to be shut off in a huge emergency where gens were dying/running out of fuel).
- jrockway 3y agoI wonder why we don't put battery backups in each server/switch/etc. Basically, just be a laptop in each 1U rack space instead of a desktop. Sure, you can't have much runtime, but if you got like 15 minutes for each device and it always worked, you could smooth over a lot of generator problems when something chews through the building's main grid connection.
- williamstein 3y agoOne challenge is that the power usage of a server is order(s) of magnitude greater than that of a laptop. This means the cost to do what you describe is significant, hence that has to be taken into account when trying to build a cluster that is competitive...
- jrockway 3y agoYeah, I agree with that. I think that power savings are a big priority for datacenters these days, so perhaps as more efficient chips go into production, the feasibility of "self-contained" servers increases. I could serve a lot of websites from my phone, and I've never had to fire up a diesel generator to have 100% uptime on it. (But, the network infrastructure uses more power than my phone itself. ONT + router is > 20W! The efficiency has to be everywhere for this to work.)
- AtNightWeCode 3y agoThey most likely lie about the power outage. Azure does this all the time. I am so fking tired of these services. Even minor data centers in Europe have backup plans for power.
- hnlmorg 3y agoIt’s pretty common to have a rack of batteries that might serve an isle. The idea of these is that you’d have enough juice for the generator to kick in. You couldn’t run these for longer periods, and even if you could, you’d still have the AC unpowered, which would quickly lead to machines overheating and crashing. Plus the building access controls need powering too. As does lighting, and a whole host of other critical systems. But the AC alone is a far more significant problem than powering the racks. (I’ve worked in places when the AC has failed, it’s not fun. You’d be amazed how much heat those systems can kick out).
- thedaly 3y agoLack of preventive maintenance if I were to guess. Also, these generators would need a supply of diesel fuel, and typically have a storage tank on site. If the diesel isn't used and replaced, it can gum up the generator.
- pard68 3y agoI've gotten 60 year old tractors to run on 60 year old diesel. Gumming up is much more common in gas applications. I guess modern diesel might not be so robust, I know almost nothing about modern engines.
- ethbr1 3y agoThere is nothing so satisfying as when an old engine with bad gas finally catches and starts running continuously.
- toomuchtodo 3y agoRunning a generator yard is just hard. You are acting as your own power utility with equipment that only runs during tests or outages. Running successfully at commissioning or during tests increases likelihood of service when needed, but is not a guarantee. https://aws.amazon.com/message/67457/ https://aws.amazon.com/message/67457/ (AWS: Summary of the AWS Service Event in the US East Region, July 2, 2012) > On Friday night, as the storm progressed, several US East-1 datacenters in Availability Zones which would remain unaffected by events that evening saw utility power fluctuations. Backup systems in those datacenters responded as designed, resulting in no loss of power or customer impact. At 7:24pm PDT, a large voltage spike was experienced by the electrical switching equipment in two of the US East-1 datacenters supporting a single Availability Zone. All utility electrical switches in both datacenters initiated transfer to generator power. In one of the datacenters, the transfer completed without incident. In the other, the generators started successfully, but each generator independently failed to provide stable voltage as they were brought into service. As a result, the generators did not pick up the load and servers operated without interruption during this period on the Uninterruptable Power Supply (“UPS”) units. Shortly thereafter, utility power was restored and our datacenter personnel transferred the datacenter back to utility power. The utility power in the Region failed a second time at 7:57pm PDT. Again, all rooms of this one facility failed to successfully transfer to generator power while all of our other datacenters in the Region continued to operate without customer impact. > The generators and electrical switching equipment in the datacenter that experienced the failure were all the same brand and all installed in late 2010 and early 2011. Prior to installation in this facility, the generators were rigorously tested by the manufacturer. At datacenter commissioning time, they again passed all load tests (approximately 8 hours of testing) without issue. On May 12th of this year, we conducted a full load test where the entire datacenter switched to and ran successfully on these same generators, and all systems operated correctly. The generators and electrical equipment in this datacenter are less than two years old, maintained by manufacturer representatives to manufacturer standards, and tested weekly. In addition, these generators operated flawlessly, once brought online Friday night, for just over 30 hours until utility power was restored to this datacenter. The equipment will be repaired, recertified by the manufacturer, and retested at full load onsite or it will be replaced entirely. In the interim, because the generators ran successfully for 30 hours after being manually brought online, we are confident they will perform properly if the load is transferred to them. Therefore, prior to completing the engineering work mentioned above, we will lengthen the amount of time the electrical switching equipment gives the generators to reach stable power before the switch board assesses whether the generators are ready to accept the full power load. Additionally, we will expand the power quality tolerances allowed when evaluating whether to switch the load to generator power. We will expand the size of the onsite 24x7 engineering staff to ensure that if there is a repeat event, the switch to generator will be completed manually (if necessary) before UPSs discharge and there is any customer impact.
- spelunker 3y agoTest your backups! Obviously easier said than done of course.
- touisteur 3y agoExperience in 'small' high availability safety-critical systems says: 1- 'failover often, failover safely'. Things that run once a month or 'just in case' are the most likely to fail. 2- people (customers) often aren't ready to pay for the cost of designing and operating systems with the availability levels they want.
- barkingcat 3y agoDatacentre administrators don't know how to run utilities. Imagine replacing the word "power" with "sewage" and try to see if you would entrust the functionality of your toilet to your local friendly sysadmin. No. You'd never ask a system administrator to administer your plumbing. Neither should you ask your system administrator to maintain a diesel power generator. Diesel generators have more in common with automobile internal combustion engines and in the high power segment, airplane jet turbines. In fact, many turbine cores are used as both airplane jet engine and as terrestrial power generation unit. You're basically asking the wrong people to maintain the infrastructure.
- pard68 3y agoWhen I worked in a DC the HVAC guys did the cooling. The electricians did the power and genset. We also had a local GE guy who did the engine part of the genset. These aren't sysadmin running generators. They are specialists hired for the job.
- linsomniac 3y agoThese experiences of power outages is weird to me. What I consider "typical" data center design should make it really hard to lose power. "Typical" design would be: Each cabinet fed by 2 ATS (transfer switch). Each ATS fed by two UPS (battery bank). Each UPS fed by utility with generator backup. The two ATS can share one UPS/generator, so each cabinet would be fed by 3 UPS+generator. A generator failing to start shouldn't be a huge deal, your cabinet should still have 2 others. The data center I'm currently in did have a power event ~3 years ago, I forget the exact details but Mistakes Were Made (tm). There were several mistakes that led to it, including that one of the ATS had been in "maintenance mode", because they were having problems getting replacement parts, but then something else happened as well. In short, they had gotten behind on maintenance and no longer had N+1 redundancy. On top of that, their communication was bad. It was snowing cats and dogs, we suddenly lose all services at that facility (an hour away), and I call and their NOC will only tell me "We will investigate it." Not a "We are investigating multiple service outages", just a "we will get back to you." I'm trying to decide if I need to drive multiple hours in heavy snow to be on site, and they're playing coy...
- mdip 3y agoYou summed up quite well how these things happen. All of these parts make for an increasingly complex system with a large number of failure points. Our DC was a very living entity -- servers were being changed out/rack configuration altered very regularly. Large operations were carefully planned. You wouldn't overlook the power requirements of a few racks being added -- there'd -- literally[0] -- be no place to plug them in without an electrician being brought in. However, in a 3-month period every once in a while, two racks would have old devices replaced either due to failure or refresh, one at a time. Since they weren't plugged directly into rack batteries (we had two battery rooms providing DC-wide battery backup), the overload wouldn't trip. Since we were still below the capacity of the circuit, the breaker(s) wouldn't trip. And maybe we're still under capacity for our backup system, but a few of the batteries are under-performing. I think the lesson we learned when this happened was: you need to "actually test" the thing. My understanding is that our tests were of the individual components in isolation. We'd load test the batteries and the generator and then the relays between. At the end of the day, though, if you don't cut the power and see what happens you don't truly know. And my understanding is that having that final step in place resulted in a large number of additional tests being devised "of the individual components" that ensured they never had an outage like that, again. [0] Guessing it's common practice to make "finding a f!cking power outlet" nearly impossible in DC. Every rack had exactly the number of leads it needed for the hardware plugged into a completely full receptacle. They rolled around a cart with a monitor, printer, label printer, keyboard, mouse and a huge UPS on it so staff could do daily maintenance work.
- nickdothutton 3y agoGenerator needs to go from 0% to almost 100% output within a period of a few seconds, UPS battery is often only a few minutes, long enough to generator to stand-up. There’s a reason why when you put your hand on the cylinder heads for that big diesel they are warm. Much like the theatre “You are only as good as your last rehearsal”.
- mdip 3y agoHad something similar happen at a telecom I worked at for years. We had a diesel generator and a couple of (bathroom sized) rooms full of (what looked like) car batteries. My understanding is that the two rooms were for redundancy. The batteries could power the DC for hours but were used only until the generator was ready. The area our DC was located in was impressively reliable power-wise and -- in fact -- the backup systems had managed through the multi-state power outage in the early 2000s without a hitch (short of nearly running out of fuel due to our fuel supplier being ... just a little overwhelmed). A few years later a two minute power outage caused the DC to go dark for a full day. Upon the power failing, the batteries kicked in and a few minutes after that the generator fired up and the DC went into holy terror. About a minute after the generator kicked in, power to the DC blinked and ended. The emergency lights kicked in, the evacuate alarm sounded[0] and panic ensued. My very pedestrian understanding of the problem was that a few things failed -- when the generator kicked in, something didn't switch power correctly, then something else didn't trip in response to that, a set of 4 batteries caught fire (and destroyed several nearby). They were extinguished by our facilities manager with a nearby fire extinguisher. He, incidentally, was the one who pulled the alarm (which wouldn't, on its own, trigger the Halon system, I think). The remainder of the day was spent dealing with the aftermath. We were a global multi-national telecom with a mess of procedures in place for this sort of thing. Everything was installed by electricians, to very exacting standards[1] but -- as with most things "backup" -- the way it was tested and the frequency of those tests was inadequate. From that point forward (going on over a decade) they thoroughly tested the battery/generator backup once a quarter. [0] We were warned to GTFO if that alarm goes off due to the flooding of chemicals that would follow a few minutes later. That didn't happen. [1] I remember the DC manager taking over in Cleveland making his staff work weeks of overtime replacing zip ties with wax lace (and it was done NASA style). We're talking thousands and thousands of runs stretching two complete floors of a skyscraper.
- uberduper 3y agoI lost track of how many datacenter outages we caused testing the power backup/failover back at eBay in the mid-2000s. There's no winning when it comes to power redundancy systems.
- uberduper 3y agoIt's not usually the battery backup or the generator that fails. It's usually the switching equipment that has to go from mains to battery to generator to battery to mains. And doing it without causing a voltage sag on the generator.