4 ms·
This is not as green as it sounds. This area of the united states suffers from huge water shortages, and the river they are using is a major source of water fo
by ars 15y ago
This is not as green as it sounds.
This area of the united states suffers from huge water shortages, and the river they are using is a major source of water for Atlanta (I'm not sure if they are upsteam or down from Atlanta).
As a result by the time the river flows out of Georgia into Alabama and Florida it is very diminished. This makes those states pretty upset since they also want to use the water.
So what does Google do? They evaporate the water! What a waste.
Water cooling is not really a very clean thing in this part of the country.
I would like to see some numbers: How much energy does it cost to desalinate the amount of water they are wasting? If it's more than the energy they are saving then they do not have a net win.
- shawnz 15y agoI don't really know anything about this, but how does water cooling consume water? Is it not just for heat transfer?
- justincormack 15y agoNot evaporative cooling.
- ceol 15y agoI would like to know why Google had to open a datacenter in that specific region. It gets incredibly hot and humid.
- jrockway 15y agoPresumably to reduce latency for nearby users. People in warm climates deserve fast Google results too! :)
- hendzen 15y agoThe amortized CAPEX (cost of building the data center) is still greater than the OPEX (cost of keeping it running). If Google can find cheap land and labor, heat might be irrelevant.
- jcampbell1 15y agoThis is an absurd argument. Evaporative cooling is green and efficient, but problematic during droughts. Your argument is like saying wind turbines are pointless because sometimes the wind doesn't blow. If Google cools with fossil fuels during only droughts, that is still much better than using fossil fuels all the time.
- learc83 15y ago>(I'm not sure if they are upsteam or down from Atlanta). The two reservoirs which provide water for Atlanta are located far north of Douglas County (I'm a resident). I do find it odd that they are using evaporation cooling, since humidity is so high here.
- ajross 15y ago"So what does Google do? They evaporate the water! What a waste." Quite literally a drop in the bucket. The back of my envelope has too much written on it at the moment, but if you look at the total water flow in that watershed and multiply it by the heat of vapoization of water you get a staggeringly large energy flow. There's no way; absolutely no way at all a few megawatts of server heating would be measurable at all. None.
- Retric 15y ago1 megawatt * 1 hour = 3,600,000,000 joules Water takes 2,257,000 joules / kg to evaporate Which works out to ~1,600 kg or 422 gallons of water per hour per MW. However, I don't think they actually want to evaporate all that much water which leaves a lot of residue issues and instead focus on heating a much larger volume of water. PS: The article is also wrong in that they don't directly cool hot air from their servers with this water. They are cooling air heated by there cooling system and depending on how hot the air from there servers are they may simply vent that if it's warmer than the outside air.
- ajross 15y agoHeh, the gauntlet has been thrown, so I need to show numbers too. I see that Atlanta rainfall is about 48" (122cm) a year. 422 gallons * 24 * 365 (* 3.785 litres/gallon) * 100 cc/L == 1.4e9 cc/year. So converting to rainfall area: 1.4e9cc/122cm = 1148 m^2 Basically a 100' square catch basin on the roof of the building would provide all the water they need. Noise.
- shabble 15y ago> Basically a 100' square catch basin on the roof of the building would provide all the water they need. Noise. Which raises the question: Why don't they just do that? I'd imagine it would be less effort to process, and even though you do need to have a buffer against low rainfall periods, water is one of the easiest things to store.
- Retric 15y ago