Thanks for the feedback. Thinking about it some more, a general purpose 1" HVAC filters are rated at about .12 in. water column at 300 feet per minute. If you'r
by rainbowzootsuit 3y ago
Thanks for the feedback. Thinking about it some more, a general purpose 1" HVAC filters are rated at about .12 in. water column at 300 feet per minute. If you're running them a lot slower by having 4x-6x area, then I could see that your tests would bear out.
I often reference this manufacturer when designing a duct system and selecting filter sizes. This is for their MERV10 filter. MERV8 is lower initial pressure. They have a velocity vs pressure chart on page 4. At 50 FPM it's down to about 0.03 in. w.c.
https://www.glasfloss.com/product/zl-hv/ https://www.glasfloss.com/product/zl-hv/
I think a centrifugal could still be an advantage for noise while having a reasonable dimension, but your feedback is sincerely appreciated.
- londons_explore 3y agoI kinda wish all filtering was done with a greatly increased surface area. A 10x increase in surface area would mean far far less powerful fans are needed, and the filters could last a decade before needing to be replaced.
- rainbowzootsuit 3y agoIn a ducted system the ductwork and air terminals reach an economic happy medium that does not really balance with trying to make the filter pressure loss the driving factor.