The vast majority of US homes use NM cable (romex) which is rated for 600v. NEC 2020 edition, Article 334 Non-Metallic Sheathed Cable 334.104 Conductors. The
by quickthrowman 3y ago
The vast majority of US homes use NM cable (romex) which is rated for 600v.
NEC 2020 edition, Article 334 Non-Metallic Sheathed Cable
334.104 Conductors.
The 600-volt insulated power conductors shall be sizes 14 AWG through 2 AWG copper conductors or sizes 12 AWG through 2 AWG aluminum or copper-clad aluminum conductors.
- ethbr0 3y agoSo the in-wall would be good, but the standard socket (NEMA 5-15) definitely isn't rated for 240v and would need upgrading.
- quickthrowman 3y agoCorrect, a residential NEMA 5-15 receptacle is only rated for 125v. There are some dual amp/dual voltage (15a/20a, 125v/250v) receptacles out there, but you almost certainly won’t see them in a house. NEMA 6-20 is rated for 20a at 250v. More dual amp/dual volt wiring devices: https://www.plugsocketmuseum.nl/NorthAm1combi.html https://www.plugsocketmuseum.nl/NorthAm1combi.html