12KW on a single phase is really not what you want to do though, that works out to 50A which is likely more than your distribution panel is wired for, usually t
by jacquesm 4y ago
12KW on a single phase is really not what you want to do though, that works out to 50A which is likely more than your distribution panel is wired for, usually they are good up to 40A and 50A for a couple of seconds but more than that and you are inviting blowing up the utility side fuses. You will also need pretty beefy cable to be able to run that kind of current, 6 mm^2 ~30A, 10 mm^2 ~40 and 16 mm^2 ~55. Unless you want to run your cable really hot, which I would not recommend. Also, you will have to beef up the wiring in your distribution panel, the utility side fuse (which normally is 3x25 or 3x35, rarely 3x50 though it is possible but will require fatter bus bars and special breakers as well). Much better to divide the power over your phases. That way you can run 12KW on 3x2.5 mm^2.
The setpoints I am struggling with are the difference between for instance the voltage at the inverter versus the voltage at the distribution panel, when pushing a mere 5KW into the grid from the upstairs inverter that raises the voltage enough that the inverter will trip. This is not due to the usual suspects (faulty wiring, loose contacts) but simply because of the length of the feedline to the attic and the fact that it is 2.5 mm square tri phase cabling, which has a 4V voltage drop over that length and there is absolutely no way to compensate for that.
Highly frustrating. Other interesting set points would be to be able to de-rate the inverter and to be able to get it to shut down faster once the sun has gone under.
That's really good value for the money what you've got there. My setup is a bit more expensive than yours but it also makes a lot more power (as it should :) ), I've spent a lot of time on getting it all set up properly for the summer. The biggest problem remaining (and that I won't be able to fix) is that I can't angle the panels on the low roof properly because that would upset my neighbors so they are at a very shallow angle, just enough to the get the water to run off them but even then at the edge of the panels in the 'down' direction there is a little area of about 5 cm where water pools long enough for algae to grow. So I will have to clean these quite frequently. Maybe I'll figure out a way to deal with that but so far nothing that really worked well. A steeper angle would require a higher starting point or a lower ending point, neither of which are feasible.
The real pay-off is in March/April and September/October when we will save substantially on gas by heating using an air/air heatpump with a COP of about 3 to 3.5 at the temperatures at that time of the year. That should put a sizeable dent in the energy costs.