19 ms·
So largely I think the confusion stems from there being two major different "types" of heat pumps and they perform very differently. The first is your conventi
by sbradford26 4y ago
So largely I think the confusion stems from there being two major different "types" of heat pumps and they perform very differently.
The first is your conventional type system, this is usually what AC units are in the US. They run at maybe 1 or 2 speeds. These type of heat pumps are common in the southern parts of the US but also will be found paired with a gas furnace in the northern US. Since they don't adjust their output dynamically they tend to start losing capacity/efficiency significantly around 25-30F.
The second is an inverter driven heat pump. You usually find these in mini splits but they can also be found in a standard air handler form factor that would replace a furnace. The inverter allows the compressor to adjust based on demand and exterior temperature to maximize efficiency. This allow these units to operate efficiently down to -13F depending on the unit. Now there will still be some capacity loss at those temps so during the design of the system this has to be taken into account.
For detailed information on the efficiency of heat pumps I would check out NEEPs website. It is a great resource, it will show you capacity and efficiency (COP) of tons of different units across their operating temperatures.
https://ashp.neep.org/ https://ashp.neep.org/