Standard non-metallic 8 gauge wire is only allowed to handle 40 amps. If you want to put 50 amps to the outlet you need more expensive wire (most likely 6 gaug
by bluGill 4y ago
Standard non-metallic 8 gauge wire is only allowed to handle 40 amps. If you want to put 50 amps to the outlet you need more expensive wire (most likely 6 gauge, but there are other forms of 8 gauge that are approved for 50 amps). Since most stoves only need 40 amps electricians will run non-metallic 8 gauge by default and put a 40 amp breaker on it - then since there isn't such a thing as a 40 amp outlet they have a 50 amp outlet on the other end.
- sbradford26 4y agoYeah the main relationship that matters is the breaker to wire. There is a fun semi related thing. Can you put 15 amp outlets on a 20 amp circuit? The answer is yes you can, but only if there is at least two receptacles, and a standard duplex outlet counts at two receptacles.
- bombcar 4y agoWhich is another reason you don't want to oversize a breaker; you can have ten, twenty two-receptacle outlets on a single circuit, and if lots of stuff was plugged in you could easily draw tens or hundreds of amps, which would melt normal Romex pretty quickly.