> Oof. A missing equipment ground (the third pin on your outlet or its wiring) will not cause these issues. In fact, it’s legal to have an ungrounded three pin
by lostlogin 4y ago
> Oof. A missing equipment ground (the third pin on your outlet or its wiring) will not cause these issues. In fact, it’s legal to have an ungrounded three pin outlet in a retrofit situation as long as it’s GFCI protected and labeled.
I’m pretty sure that this is location specific and I don’t think this was pass where I am. Even outlets which aren’t RCD protected get a fail now.
- amluto 4y agoYou must be somewhere that calls them GFCIs RCDs. :) This particular rule in the NEC (the code for most US jurisdictions) only allows this as a retrofit: https://www.electricallicenserenewal.com/Electrical-Continuing-Education-Courses/NEC-Content.php?sectionID=306.0 https://www.electricallicenserenewal.com/Electrical-Continui...
- lostlogin 4y agoNot going to lie, that's above me. But is that allowing outlets that aren't grounded? If so, yikes. I'm in New Zealand and if you are touching your electrics when getting work done, you need to be installing RDCs on the circuit. You can do all sorts of stupid things when you have an RCD on a circuit, and while I'm sure you could still get electrocuted, you'd have to try quite hard. https://www.nhpnz.co.nz/en/News/Stay-safe-with-compliant-RCDs https://www.nhpnz.co.nz/en/News/Stay-safe-with-compliant-RCD...
- amluto 4y agoGFCI is American for RCD, more or less. Except that our GFCIs are almost always 5mA, whereas yours seem to mostly be 30mA. And ours don’t generally live on DIN rails. The rule here is that, if you replace an old ungrounded outlet, you ought to find a way to ground it and, if you can’t, you must add a GFCI. (Sadly this often can’t be done in the breaker box, so it means a GFCI in the receptacle. The issue with adding GFCIs in the breaker box is that a lot of old knob and tube installations didn’t match up neutrals with their corresponding hots, so individual circuits don’t have circuit-specific neutrals to run through the GFCI.) American GFCI breakers generally look like this: https://www.homedepot.com/p/Square-D-Homeline-20-Amp-Single-Pole-GFCI-Circuit-Breaker-HOM120GFICP/100002959 https://www.homedepot.com/p/Square-D-Homeline-20-Amp-Single-...