>If one line has a large load relative to the other, the neutral won't be that close to ground. Shouldn't it still be pretty close voltage wise? If we hold the
by xxpor 4y ago
>If one line has a large load relative to the other, the neutral won't be that close to ground.
Shouldn't it still be pretty close voltage wise? If we hold the neutral is always at 0v at the panel, since that's where it's tied to ground, the voltage on the neutral between the panel and the outlet should still be pretty low because copper wire has a pretty low resistance (by V=IR). I'd have to break out my calculator (and look up the actual standard values of copper wire resistance), but I'd guess even >20V would be quite unusual without some other fault...
- galangalalgol 4y agoAt dc for sure, at 60hz perhaps imaginary impedance could create "spicy case". I only thought about it because I used to use a welding cable adapter for my dryer port that had a "bootleg ground" and the internet warned me a shock from the case could be a result.