3 ms·
Page 79 has a bit of info on COP (efficiency) vs LLT (leaving liquid temp). With intelligent management of LLT, your install will spend a lot of the year at 12
by sokoloff 4y ago
Page 79 has a bit of info on COP (efficiency) vs LLT (leaving liquid temp).
With intelligent management of LLT, your install will spend a lot of the year at 120°F or lower, where the efficiency is fairly high. If you end up with 2-3 days of COP under 2.0, that’s not catastrophic if you spend 40-50x as much of the season at COP of 3.5+.
You can probably find the outdoor temperature histogram for your area and figure out what your overall heating profile looks like.
But, if you need 150°F water a lot, AWHPs are probably not a good fit.
- contravariant 4y agoOh were the temperatures mentioned in Fahrenheit? Then that makes things a bit easier, I thought they needed 150°C.
- sokoloff 4y agoIn that article (for industrial process heating), it could be in °C. For home heating, 150°C would be far too dangerous to circulate.
- nkurz 4y agoNo, the temperatures are in Celsius. From the white paper linked from the main article: "This paper makes a distinction between low temperature (<200°C) and high temperature (>200°C) process heat". https://www.sintef.no/globalassets/sintef-energi/industrial-heat-pump-whitepaper/2020-07-10-whitepaper-ihp-a4.pdf https://www.sintef.no/globalassets/sintef-energi/industrial-...
- hanche 4y agoYour original guess is right. I checked the original Norwegian text. It says 150 grader (degrees), and that surely means Celsius when used unqualified in Norwegian. So we’re talking high pressure superheated water here, for industrial purposes.
- MobiusHorizons 4y agoAnother clue is that they call 150 deg 5 bar steam.
- ZeroGravitas 4y agoNote that the article talks about a different design of heat pump, compared with the common home and industrial HVAC units, for use in industry at that higher temp. Especially valuable when you have some waste heat from another process. Probably a good fit for existing district heating systems too.