> Building was evacuated within 4 minutes. > Concerning the construction, how common is it to have a 1-h fire resistance? Fire rating requirements are for huma
by toast0 4y ago
> Building was evacuated within 4 minutes.
> Concerning the construction, how common is it to have a 1-h fire resistance?
Fire rating requirements are for human safety and not really property safety. In this case, 1 hour rating was more than sufficient for everyone to exit.
The type of use/occupancy of the building generally sets the requirements; I don't know requirements for data centers. 1 hour is kind of the start of enhanced fire ratings; some things might not have a requirement of even 1 hour, others may have more. A large enough fire rating (again, depending on use), may be considered a firewall which can be used to consider each side a seperate building for fire planning purposes. A smaller, but still large rating may be needed to partition spaces with different needs. Higher ratings are common for stairwells, and I wouldn't be surprised if they were required for the battery room and other areas of concentrated risk.
> Why don't we convert all the power to DC in a central location before feeding DC power to the servers ?
Some datacenters do run servers on DC, typically phone companies, and typically -48VDC. This has pros and cons. You may simplify power conversion from batteries, and the ac -> dc input step will likely clean the power, too. But 48v is much lower than common AC voltages, and lower voltage means more current for the same power, which means more loss in transmission and larger conductors required and more heat generated as well.
You still need individual power supplies on each computer, as you need to go from -48v to +12v (and maybe some others, depending). Historically, DC/DC voltage conversion was much less efficient than AC/DC, but that's less true today.
Well designed AC switching can happen at the zero crossing, which can reduce arcing, which is sometimes useful.