Why should battery rooms be inside buildings? Backup generators aren’t.
by gumby 4y ago
Why should battery rooms be inside buildings? Backup generators aren’t.
- WatchDog 4y agoAt this site I think the generators are outside, but there are lots of facilities that keep their generators inside the main structure.
- gumby 4y agoInteresting — I was about to say “I’ve never seen one inside” but realize what I really should say is, “I only notice them when they are outdoors”
- slenk 4y agoMy old company had flywheel generators - since those didn't generate pollution they all were located inside
- deleted 4y ago[deleted]
- Narkov 4y agoFlywheel generators or UPS? AFAIK, flywheels are only temporary energy stores while diesel gensets are spun up to peak power.
- gumby 4y agoThey are also used as frequency/power regulators (or for high power phase conversion, unlikely in a data center)
- slenk 4y agoFlywheel while the diesel gennies spun up
- c_o_n_v_e_x 4y agoDRUPS - Dynamic rotary UPS. It provides enough energy for your ride-through period until your gensets are up and the power quality is good.
- nine_k 4y agoSome facilities keep generators either on the technical floor, or on the roof. AFAICT putting out relatively small hydrocarbon fires is done efficiently with water and foaming agents that cut off the air supply. As soon as the generator is not producing electricity, these measures can be used. Batteries though cannot be switched off, and using water around serious electrical currents is a very, very dangerous idea. It's already much harder to put out a fire around lead-acid batteries, and nigh impossible with Lithium-based batteries. This is where you need actual physical firewalls which can withstand fire for a long time and not let it through.
- tyingq 4y agoSeems counter-intuitive because they are also used in vehicles, but lead acid batteries last much longer in an in air conditioned environment.
- jhugo 4y agoAt a place I worked years ago ours was inside, in a fireproofed and soundproofed room, with a giant intake vent to the outside and exhaust chimney to the roof.
- c_o_n_v_e_x 4y ago1. Lead acid batteries need to be between -20C to +50C for charging or discharging. 2. Especially in hot climates, inverters in the UPS need to be kept cool. 3. I assume that by keeping the UPS & batteries inside the building, you minimize transmission loss/voltage drops so you don't have to oversize your conductors.