6” to the top of the conduit for IMC and RMC. 18” to the top of PVC conduit (12” for 120V, GFCI protected, 20A max overcurrent protection). If you’re willing t
by sokoloff 5y ago
6” to the top of the conduit for IMC and RMC.
18” to the top of PVC conduit (12” for 120V, GFCI protected, 20A max overcurrent protection). If you’re willing to put 2” of concrete over it, PVC drops to just 6”.