Putting signalling and power wires in the same conduit is about as bad as it gets. The proper way to do this is to dig a trench and use armored cable suitable
by jacquesm 5y ago
Putting signalling and power wires in the same conduit is about as bad as it gets.
The proper way to do this is to dig a trench and use armored cable suitable for burial without further protection and to use a plastic uninterrupted tube for the cat6 (which you can blow through).
That said, there isn't a lot of difference between a DIY person and a low grade contractor, and a competent DIY'er is probably better than most mid level contractors. The big difference is usually that they have the tools and they're with a couple of people and you're just by your lonesome.
- raytube 5y agoJust expose the armoured cable. Hardly an issue, and you know where it is.
- jacquesm 5y agoNot a good idea. The outer layer is plastic, underneath that something that is best described as an oversized shower hose. Burying it will allow you to take vehicles, wheel barrows, lawnmowers etc over it without damaging it. I bought a ton of this stuff surplus from a dam construction, that served me quite well in Canada, some of the outbuildings were quite far away from the main house. It's pretty easy to work with, though stripping it is a bit of an art (you really don't want to damage the inner wires).
- 0xbadcafebee 5y agoThe author's shed is about 2 feet from the house exterior, so he can wrap the steps around as decking (very tiny decking) and put the cable under the steps.
- kevin_thibedeau 5y agoThen one day someone cuts up that decking with a sawzall and gets an unexpected surprise.
- jacquesm 5y agoThat's possible, but you'd need to clearly mark it. For two feet it's overkill, but normally, especially if there is the possibility of going between the two structures, you'd dig down 4', lay down your cable so that it is going down vertically in both structures and is well below the frost line where you bury it horizontally.
- ErrantX 5y agoYou can get armoured cable specifically with UV rating for this. I'd only ever run it against a wall etc. But it is designed to be above ground.
- jacquesm 5y agoYes, true. That cable has a special marking and there are even kinds that are solid enough to be driven over with tired vehicles. But those are super expensive, far more expensive than the kind that can be buried, and they are serious work to strip and connect. In a lot of cable that I bought there was one chunk of that stuff, about 2" thick for what looked to be tri phase, 40A+ground (so five wires + the steel cover). Bending radius about a mile :) I'm sure there are thinner more pliable versions of that stuff available as well and I sometimes see the equivalent tie wrapped for temporary industrial applications to cranes and bridges.
- stickfigure 5y agoIt's short. Put a normal extension cord in the "conduit", with plugs on each end. At least here in California, electrical code ends at the receptacle. You can do practically anything you want on the other side, as long as it plugs in.
- sgtnoodle 5y agoI'm pretty sure it's against code in CA to install an extension cord permanently inside a structure or conduit like that. When I put all the cables in the wall for my TV, I ran Romex from the bottom junction box to the top junction box, despite the bottom junction box having a male electrical plug. An extension cord plugs into that from another outlet. (Ideally I would have just hardwired the upper outlet, but that would have been another can of worms.)
- jacquesm 5y agoThat trick won't work. An extension cord is only seen as such as long as it is not permanently attached to a structure, and definitely not when it powers a fixed structure. In other words, it needs to be temporary and to be disconnected when not in use. As soon as you connect it permanently affix it or bury it you are violating the electrical code. Otherwise this would act as a giant loophole around the electrical code, you could simply use a high current plug to connect your distribution panel and call it a day. https://plasticinehouse.com/can-i-use-an-extension-cord-to-power-my-shed/ https://plasticinehouse.com/can-i-use-an-extension-cord-to-p...
- stickfigure 5y ago> Otherwise this would act as a giant loophole around the electrical code ...it basically is? People use it that way. All the time. Whether or not you like like that, it's the way it is. Personally I'm pretty ok with it. This guy is not actually going to kill someone with his shed.