It's a simple formula, the CoP, I linked it in my above post. The below PDF has a chart of temps to efficiencies. 47F will be around 100% efficiency or a CoP o
by hunterb123 5y ago
It's a simple formula, the CoP, I linked it in my above post.
The below PDF has a chart of temps to efficiencies. 47F will be around 100% efficiency or a CoP of 1. New York winter days are generally below that.
https://www.energy.gov/sites/prod/files/2017/04/f34/2_32219_Shen_031417-0900.pdf https://www.energy.gov/sites/prod/files/2017/04/f34/2_32219_...
That's a potential 40% energy loss. 20% at the plant, 20% at the house.
It all depends on the region's temperature. Electric heating is more efficient in some places, less efficient in some, and equal in some.
For New York, it does not make sense to use a heat pump:
https://www.currentresults.com/Weather/New-York/Places/new-york-city-temperatures-by-month-average.php https://www.currentresults.com/Weather/New-York/Places/new-y...
- johncolanduoni 5y agoThat document lists the COP for an electric heat pump with an external temperature between 35F and 40F at around 3.25. The definition from the article you linked defines COP as “ ratio of useful heating or cooling provided to work (energy) required”. So at that temperature range, it’s still heating more than it’s consuming energy. A natural gas space heater cannot exceed a coefficient of performance of 1 (it would violate energy conservation). You’re still not comparing the same types of efficiencies, they have different denominators.