Wouldn’t a UPS + generator failover mean that the HW never spins down in the first place? That’s how I interpreted op’s statement anyway.
by vlovich123 5y ago
Wouldn’t a UPS + generator failover mean that the HW never spins down in the first place? That’s how I interpreted op’s statement anyway.
- jacquesm 5y agoI've seen plenty of UPS's fail, and generator failover is that moment when everybody stands there with their fingers crossed. None of those things are fool proof and in case of a large scale outage, especially one that lasts more than a couple of minutes there is a fair chance that you will find the limitations of some of your contingency plans.
- acdha 5y agoHopefully, but those aren't perfect. Large data centers regularly test those because things can go wrong with any of the UPS, generator[1], or the distribution hardware which switches between the line and generator power. One of the longer outages I've seen was when the distribution hardware itself failed and burnt out multiple parts which the manufacturer did not have sufficient spares in our region. AWS has a lot of very skilled professionals who are quite familiar with those issues so I'd be quite surprised if it turned out to be something that simple but you always want to have a contingency plan you've tested for what happens if core infrastructure like that fails and takes multiple days to recover. 1. One nasty example: fuel issues which aren't immediately obvious so someone doing a 5 minute test wouldn't learn that the system wasn't going to handle an outage longer than that.