Usually when someone claims T3+ they mean they have UPS clusters in 3+1 (or such) configuration and two different such UPS clusters power two power-strips in a
by vinay_ys 5y ago
Usually when someone claims T3+ they mean they have UPS clusters in 3+1 (or such) configuration and two different such UPS clusters power two power-strips in a rack. Then, would also have incoming grid power supply from two different HV sub-stations with non-intersecting cable paths. They would also have diesel power generators in 3+1 or 5+2 configurations with automatic startup time in seconds. The UPS's power storage (chemical or potential energy based devices) can hold enough energy to handle full load for several minutes. If these are design and maintained correctly, even while concurrent scheduled maintenance is ongoing, an unexpected component failure should not cause catastrophic outage.
At each layer (grid incomers, generator incomers, UPS power incomers) there are switches to switch over whenever there's a need (maintenance or failure).
If they claim tier4, then they basically have everything in n+n configuration.
- tyingq 5y agoThough that doesn't match very well with "uninterruptible power supply units can be engaged for certain functions". It sounds worded to convey that the UPS is limited in some way. An interesting old summary of their 2012 us-east-1 incident with power/generators/ups/switching: https://aws.amazon.com/message/67457/ https://aws.amazon.com/message/67457/