3 ms·
I wonder if it is prohibitively expensive to do a real life system test on a big data center It's probably prohibitively dangerous. Backup power systems don't
by cperciva 15y ago
I wonder if it is prohibitively expensive to do a real life system test on a big data center
It's probably prohibitively dangerous. Backup power systems don't have many-nines of reliability; generators which are reliable enough for the once-a-decade event when a car crash knocks out your utility power aren't anywhere near the reliability needed to run your datacentre for an hour every month as a test.
- ams6110 15y agoOn the other hand, just as with database backups, making them is only half of the story. You have to test restores/recovery. Does your plan actually work? What have you overlooked? What edge cases do you need to accommodate? Many data centers will test backup power generation regularly just for this reason. It's not unheard of at all and the risk of a problem at a planned time is worth the confidence in knowing that the system is more likely to work when needed at an unexpected time.
- emaste 15y agoActually, if you don't run test your generator regularly it's very unlikely to work when you do need it. Here's a doc from cummins, a generator mfgr: http://www.cumminspower.com/www/literature/technicalpapers/PT-7004-Maintenance-en.pdf http://www.cumminspower.com/www/literature/technicalpapers/P... It claims that the generator should be run for 30 minutes every month, loaded to at least one third of the rated capacity. So testing every month is exactly what you want to do.
- rdl 15y agoRight, but the thing you don't test is the transfer switch/sync gear. Powering up the generator and dumping the output as heat weekly is pretty standard practice.
- ams6110 15y agoAlso don't forget to check the fuel tanks. With the rise in fuel prices the past couple of years, theft of diesel from backup generators has become more common.
- Game_Ender 15y agoIn general active engines (and fuel) don't store well. They are full of lots of seals and fluids that need to be exercised periodically to function correctly. As someone else posted generator manufacturers recommend running them once a month to keep them in good working order. The same is true of a car, leave it parked in one place for too long, and you are going to have trouble starting or driving it.