It's normally set that high by design because the solar panels have substantial capacitance to ground (they are large flat conductors sat just a few cm off the
by londons_explore 5y ago
It's normally set that high by design because the solar panels have substantial capacitance to ground (they are large flat conductors sat just a few cm off the ground after all). The capacitance to ground wouldn't be an issue if not for the fact the inverter is non-isolated. That means current can flow to/from the grid to charge and discharge that capacitor, which is indistinguishable from AC leakage.
Some inverters will allow you to lower the leakage threshold (usually with settings in a service menu), but then you're limited to just attaching 3 or so panels or getting false isolation trips.
- Filligree 5y agoIn my case the panels are, in fact, mounted on wooden brackets a good 1.5 meters off the ground. On the other hand, there's 20 m^2 of them.