RGB-life liquidcooling != Data Center liquid cooling They have precision dry break quick connects. They use crazy jacketed hoses with PTFE liners and copolymer
by intpx 5y ago
RGB-life liquidcooling != Data Center liquid cooling
They have precision dry break quick connects. They use crazy jacketed hoses with PTFE liners and copolymer sheating, sometimes with reinforcment layers. The coolant is pumping through at an operating pressure of 10bar @ 200C. These applications exceed the limits of potable water and hydronic heating systems
- deleted 5y ago[deleted]
- namibj 5y agoFor what reason would a datacenter operate 200C coolant?
- bob1029 5y agoThe only reasonable thing I can come up with is we got an extra 0 here. 20C/68F sounds like a more practical temperature for keeping the computers alive.
- namibj 5y agoIt's actually quite cold, if you're thinking of water blocks on the chips. It does fit if you're thinking of air-to-water heat exchangers to cool the hot exhaust of a google rack before recirculating. Something closer to 30C or even 40-45C (the latter if you're in a hot and humid location like Florida and want to get by without refrigeration technology and just increasing the flow rate/heat exchangers) is more realistic for datacenter-scale component-level water cooling. Yeah, a high-power-density Nvidia chip may need colder water in the 20-30C range, but CPUs and such aren't efficient at the clocks that cause power densities where you need <<40C water. My 5950X is running at ~30C (return from the radiator) water and 4.5 GHz (maybe even a bit more? I don't recall, the heat wave around here is over) on a torture test with Prime95 where it produces almost double the nominal TDP (thermally limited, due to a few hot-running cores and around 80-85C average core temperature on the others). The base clock is at just 3.4 GHz. I see phase-change cooling with nucleate boiling as well as very tightly integrated (liquid) water channels in the future, with the latter thinning out the die to weld or solder a better thermal conductor closer to the actual transistor junctions, with minimal distance to the coolant.
- KaiserPro 5y ago10 bar to the rack that seems a bit high? How does the coolant get to 200c, that'd imply some sort of inline heatpump right?