We're taking a different approach in Australia (the state of Victoria specifically), and not only are we replacing bare wire overheads with buried cables [0], w
by dthunder 5y ago
We're taking a different approach in Australia (the state of Victoria specifically), and not only are we replacing bare wire overheads with buried cables [0], we are also implementing Rapid Earth Fault Current Limiter (REFCL) technology to lower the risk of bushfires due to downed wires. [1]
When powerlines come into contact with the ground or a tree, arcing can occur. If the line remains live and continues arcing, the risk of fire is quite high.
REFCL tech works by detecting the phase-to-earth faults that occur when a one of the three-phase powerlines breaks and falls to the ground. REFL instantly reduces the voltage on the fallen line, and boosts the voltage on the other two phases. REFCL will then test the faulted line after a few seconds, and if the fault was intermittent full service is restored. If not, the whole line is removed from service to prevent fires and make the line safe to work on.
On Total Fire Ban days (very high risk of fire due to weather conditions), the REFCL settings operate at increased sensitivity.
There's a requirement in Victoria that by 2023 all high risk zone substations have to install REFCL technology, and all HV customers connected to those zone subs have to be REFCL compliant (their equipment must be able to handle the over-voltages that occur during REFCL operation).
[0] https://www.energy.vic.gov.au/electricity/powerline-replacement/powerline-bushfire-safety-program/network-assets-program/high-voltage-network-assets-program https://www.energy.vic.gov.au/electricity/powerline-replacem...
[1] https://www.energy.vic.gov.au/safety-and-emergencies/powerline-bushfire-safety-program/network-assets-program/rapid-earth-fault-current-limiter-refcl https://www.energy.vic.gov.au/safety-and-emergencies/powerli...
- avidiax 5y ago> REFL instantly reduces the voltage on the fallen line, and boosts the voltage on the other two phases. I didn't get how that would work, so I did a bit of research. REFCL effectively grounds the affected phase so that it is 0V with respect to ground. But the other 2 phases retain the same voltage relative to the affected phase, so they have increased voltage relative to ground. https://www.ausnetservices.com.au/-/media/Files/AusNet/Community/REFCL-Fact-Sheet-3-HV-customer-solutions-v2.ashx?la=en https://www.ausnetservices.com.au/-/media/Files/AusNet/Commu...
- Andys 5y agoAdditionally, we have increased patrols of the wires in regional areas, installation of spreader bars, and regular clearing of the trees and shrubs near the wires.
- ikr678 5y agoNot using bundled/sheathed ABC overhead cable? Or was that too expensive relative to the remaining risk.
- stephen_g 5y agoI'm not super familiar with power systems, but as far as I've seen in Australia, higher voltage ABC mostly only comes in 11 or 22kV (distribution), not 33kV and up which this seems to be talking about (feeder/transmission). You do seem to be able to buy 33kV ABC from China but not sure if it would meet Australian Standards. Looking at Wikipedia's page on ABC though, it says that even older 11/22kV ABC is being replaced to underground in Australia because the insulation can degrade and it can cause fires too.