I have been in this situation , maintenance on cooling tower 1 engineer put it into bypass mode so he can work on it safely (in case bms decides to turn it on w
by brentcetinich 5y ago
I have been in this situation , maintenance on cooling tower 1 engineer put it into bypass mode so he can work on it safely (in case bms decides to turn it on while he is on it.) When he left the site he forgot to take it out of bypass mode. every few days the BMS rotates the cooling towers switched off tower B and turned on tower A which was still in bypss mode… so air was blowing but the water was not circulating. the temperature graphs show the effected floors of data Center space heat up very quickly. there was a lot of permanently damaged equipment 24/7 human operators ignored many warning about ambient temperature and Low humidity assuming it was system error ( does it look hot on the cameras?? shrug ?? ) various equipment have different power down temperatures the halon did not trigger for us. some equipment did not for whatever reason shutdown when they hit the cutoff temps and cooked themselves. I suspect the Low humidity caused too much static and that’s where the damage was from..
I guess thats something hard to test for , let’s put this switch in an oven and run it to make sure it auto powers down at 80c :) every time we release a firmware.
was a problem from multiple vendors who issued bios / firmware patches. Cisco, dell, Emc, brocade.