In theory, the C13/C14 connection has a longer earth pin than live and neutral, and it should dissipate all the load while unplugging. That earth pin just zapp
by bayindirh 6y ago
In theory, the C13/C14 connection has a longer earth pin than live and neutral, and it should dissipate all the load while unplugging.
That earth pin just zapped me only once in 15 years, I don't remember what brand it was, however it was a beefy (750W+) server PSU.
Any acceptable quality PSU has internal bleed resistors to prevent shocks AFAICS.
- fsh 6y agoThe PE connection is exclusively for grounding exposed metal parts and is not allowed to carry any current during normal operation. Using it to discarge capacitors would probably trip the RCD circuit in a modern installation. What you really need is a bleeder resistor between the terminals of high-voltage capacitors.
- walrus01 6y agoThough some TVs now come with a two pin IEC connector only...
- bayindirh 6y agoJust asking due to curiosity: Do modern TVs need high voltage circuits unless they're plasmas? Also, are there any standards which force internal bleeding if there's no earth connection?
- elsjaako 6y agoI'm not sure about the other one, but: >Do modern TVs need high voltage circuits unless they're plasmas? The way a lot of power supplies work, is that they rectify the 110V/230V to a reasonably high DC value, and change that to a high frequency AC signal so it can be transformed to a lower voltage with a smaller transformer. This means there's typically some capacitors charged with sqrt(2) * line voltage during normal operation.
- bayindirh 6y ago> This means there's typically some capacitors charged with sqrt(2) * line voltage during normal operation. Thanks. Didn't know that.