2 ms·
Here is an update from AT&T: The front 1/3rd of the building is structuraly damaged. That includes fiber entry. They have no power and there is major flooding
by iJohnDoe 6y ago
Here is an update from AT&T:
The front 1/3rd of the building is structuraly damaged. That includes fiber entry.
They have no power and there is major flooding on all floors including the basement.
The Fire Department is en route with pump trucks to help with the flooding.
They have Building Engineers and Electricians on the way to look into the structure and getting power turned on.
They have 2 850KW generators on the way and 2 1MW generators on standby.
They have new A/C Chillers on the way (Existing Chiller plant was destroyed).
- onionisafruit 6y agoThis post from reddit has a bit more information...although it's mostly the same information in slightly different format. https://www.reddit.com/r/nashville/comments/kkcwkh/status_of_the_att_noc_on_2nd_from_a_friend/ https://www.reddit.com/r/nashville/comments/kkcwkh/status_of... "The Nashville building (NSVLTNMT) has sustained significant structural damage to the front one-third of the building; the rear two-thirds of the building appears to be intact. Parts of the interior are still inaccessible for safety reasons due to the structural damage sustained. Structural and electrical engineers are en route. There is standing water in the basement and on every floor. The fire department will assist with pumping water out of basement. There is no commercial power connectivity to the equipment due to breaker and switch equipment damage. Teams are currently working to de-energize all systems. Two 850W generators are en route with an ETA of 21:00 CT. A chiller is also en route with no ETA available at this time. The parking lot adjacent to the building (opposite the damaged side) has been secured to stage the generators. Once the generators arrive, teams will determine if it is safe to wire the generators tonight due to the sustained building damage and water in the building. In addition, TEMA (Tennessee Emergency Management Agency) is volunteering two 1 megawatt generators to support recovery. A SATCOLT has been positioned approximately a block and a half from the NSVLTNMT building and is up and taking traffic to aid in communication with those performing restoration. The next update will be issued at approximately 20:00 CT, unless there is a significant change in status."