As we were growing, we slowly converted a telco hardware server room into a real server room. Knocked out a wall to get enough room volume for a mini-split AC,
by hinkley 6y ago
As we were growing, we slowly converted a telco hardware server room into a real server room. Knocked out a wall to get enough room volume for a mini-split AC, removing the sprinkler head, moving the servers... And replaced all the wiring with plugs higher on the wall so that flooding wouldn't result in an electrical fire.
So when it came time to move our staging database over to the new wiring, the head of IT unplugged the UPS from the wall, the UPS complains like UPSes are wont to do in such situations, and in the time it took him to untangle the cable and plug it into the new circuit, the UPS dies. Bad batteries that the health checks didn't detect. Unplanned shutdown of our shared database. Whups.
And that is when management was taught about redundant power supplies, and periodic UPS maintenance.
- dervjd 6y ago|And that is when management was taught about redundant power supplies, and periodic UPS maintenance. And hopefully about setting up monitoring on your UPS to keep track of battery health ;)
- hinkley 6y agoThe UPS was reporting as green. Not so much you can do when the hardware is lying to you.