I've had at least a hundred times more power outages due to protection devices tripping (usually true positives) than the grid going down, so spending 20 minute
by formerly_proven 6y ago
I've had at least a hundred times more power outages due to protection devices tripping (usually true positives) than the grid going down, so spending 20 minutes to figure out which socket would be the best choice to hook all the communications stuff up to is a much better investment than buying an UPS. FWIW, I had more downtime with the UPS than through actual grid outages because the UPS didn't like a battery hotswap and powered off, or because the batteries started to gas off hydrogen sulfide, which required disconnecting them immediately, but the UPS then powered down (without a battery) and couldn't start without one, either, so it required rewiring a little bit to get going again.
Edit: My UPS is a line-interactive rack-mount APC unit, which as I understand things don't actually contain a power supply, so everything runs from the battery voltage and is supported by the charger in mains operation, but without a battery inserted the charger doesn't work, because its control circuit is powered by the battery.